background image

2/12

EX-RC1 

R e m o t e   I / O   Ad a p t e r

Unitronics

5

Wiring Procedures

Use crimp terminals for wiring; use 26-14 AWG wire (0.13 mm 

2

–3.31 mm

2

) for all wiring purposes. 

1.

Strip the wire to a length of 7±0.5mm (0.250–0.2.08 inches).

2.

Unscrew the terminal to its widest position before inserting a wire.

3.

Insert the wire completely into the terminal to ensure that a proper connection can be made.

4.

Tighten enough to keep the wire from pulling free.

To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·cm).
Do not use tin, solder, or any other substance on stripped wire that might cause the wire strand to break.
Install at maximum distance from high-voltage cables and power equipment.

Wiring Power Supply 

Connect the "positive" cable to the "+V" terminal, and the “negative” to the "0V" terminal. 

Earthing the Power Supply 

To maximize system performance, avoid electromagnetic interference by: 

Mounting the module on a metal panel.
Earthing the module’s power supply: connect one end of a 14 AWG wire to the chassis signal;
connect the other end to the panel.

Note: If possible, the wire used to earth the power supply should not exceed 10 cm in length.  However, it is 
recommended to earth the module in all cases.  

POWER

0V

V

Summary of Contents for EX-RC1

Page 1: ...understand this document and any accompanying documentation All examples and diagrams shown herein are intended to aid understanding and do not guarantee operation Unitronics accepts no responsibility for actual use of this product based on these examples Please dispose of this product in accordance with local and national standards and regulations Only qualified service personnel should open this...

Page 2: ...sconnect the device when the power is on Environmental Considerations Do not install in areas with excessive or conductive dust corrosive or flammable gas moisture or rain excessive heat regular impact shocks or excessive vibration Leave a minimum of 10mm space for ventilation between the top and bottom edges of the device and the enclosure walls Do not place in water or let water leak onto the un...

Page 3: ...tronics 3 Screw Mounting The figure below is not drawn to scale It may be used as a guide for screw mounting the module Mounting screw type either M3 or NC6 32 4mm 5 8mm 0 228 85mm 3 346 80mm 3 15 68 4mm 2 693 93mm 3 66 4mm x2 0 16 0 16 ...

Page 4: ...otective cap provided with the adapter This cap covers the port of the final I O module in the system To avoid damaging the system do not connect or disconnect the device when the power is on 1 2 Component identification 1 Module to module connector 2 Protective cap Wiring Do not touch live wires Unused pins should not be connected Ignoring this directive may damage the device Double check all wir...

Page 5: ... kgf cm Do not use tin solder or any other substance on stripped wire that might cause the wire strand to break Install at maximum distance from high voltage cables and power equipment Wiring Power Supply Connect the positive cable to the V terminal and the negative to the 0V terminal Earthing the Power Supply To maximize system performance avoid electromagnetic interference by Mounting the module...

Page 6: ...communicates via Unitronics proprietary UniCAN protocol UniCAN can comprise up to 60 nodes including PLCs and EX RC1 remote I O adapters The CANbus port is galvanically isolated CANbus Wiring 121 terminating resistor 121 terminating resistor Circuit protection device 24V Power Supply V L H V PE V L H V PE V L H V PE Network terminators Place terminators at each end of the CANbus network Resistance...

Page 7: ...1 Remote I O Adapter Unitronics 7 Network Layout The EX RC1 enables you to remotely locate I Os up to 1 kilometer from a PLC You can include both PLCs and adapters on the UniCAN network up to a total of 60 nodes ...

Page 8: ...per unit Galvanic isolation Yes between CANbus and adapter Cable type Twisted pair DeviceNet thick shielded twisted pair cable is recommended Cable length baud rate 25 m 100 m 250 m 500 m 500 m 1000 m 1000 m 1 Mbit s 500 Kbit s 250 Kbit s 125 Kbit s 100 Kbit s 50 Kbit s 20 Kbit s If you require cable lengths over 500 meters contact technical support Environmental IP20 NEMA1 Operating temperature 0...

Reviews: