background image

  IO-DI8-RO8, IO-DI8-RO8-L   

I / O   E x p a n s i o n   M o d u l e s

5/05

 

 

Unitronics 

 

 

 

Connecting Expansion Modules 

An adapter provides the interface between the OPLC and an expansion module. To connect the I/O module to 
the adapter or to another module: 
1. 

Push the module-to-module connector into the port located on the right side of the device. 

Note that there is a protective cap provided with the adapter.  This cap covers the port of the 

final  

I/O module in the system. 

 

„

 

To avoid damaging the system, do not connect or disconnect the device when the  
power is on. 

 

Component identification 

1 Module-to-module 

connector 

2 Protective 

cap 

 

 

1

2

 

Wiring 

 

 

„

 

Do not touch live wires. 

 

„

 

Unused pins should not be connected.  Ignoring this directive may damage the device. 

„

 

Do not connect the ‘Neutral or ‘Line’ signal of the 110/220VAC to the device’s 0V pin. 

„

 

Double-check all wiring before turning on the power supply. 

 

Wiring Procedures 

Use crimp terminals for wiring; use 26-12 AWG wire (0.13 mm 

2

–3.31 mm

2

) for all wiring purposes. 

1. 

Strip the wire to a length of 7±0.5mm (0.250–0.300 inches).  

2. 

Unscrew the terminal to its widest position before inserting a wire.  

3. 

Insert the wire completely into the terminal to ensure that a proper connection can be made. 

4. 

Tighten enough to keep the wire from pulling free.  

„

 

To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·cm). 

„

 

Do not use tin, solder, or any other substance on stripped wire that might cause the wire strand to break. 

„

 

Install at maximum distance from high-voltage cables and power equipment. 

I/O Wiring—General 

„

 

Input or output cables should not be run through the same multi-core cable or share the same wire. 

„

 

Allow for voltage drop and noise interference with input/output lines used over an extended distance.  
Use wire that is properly sized for the load.  

„

 

The adapter and I/O signals must be connected to the same 0V signal. 

 

Summary of Contents for IO-DI8-RO8-L

Page 1: ...itronics accepts no responsibility for actual use of this product based on these examples Please dispose of this product in accordance with local and national standards and regulations Only qualified service personnel should open this device or carry out repairs User safety and equipment protection guidelines This document is intended to aid trained and competent personnel in the installation of t...

Page 2: ...derations Do not install in areas with excessive or conductive dust corrosive or flammable gas moisture or rain excessive heat regular impact shocks or excessive vibration Leave a minimum of 10mm space for ventilation between the top and bottom edges of the device and the enclosure walls Do not place in water or let water leak onto the unit Do not allow debris to fall inside the unit during instal...

Page 3: ...odules Unitronics 3 Screw Mounting The figure below is not drawn to scale It may be used as a guide for screw mounting the module Mounting screw type either M3 or NC6 32 4mm 5 8mm 0 228 85mm 3 346 80mm 3 15 68 4mm 2 693 93mm 3 66 4mm x2 0 16 0 16 ...

Page 4: ...k all wiring before turning on the power supply Wiring Procedures Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm 2 3 31 mm 2 for all wiring purposes 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Insert the wire completely into the terminal to ensure that a proper connection can be made 4 Tighten enough ...

Page 5: ...ource or npn sink inputs npn sink inputs pnp source inputs 0V V Circuit Protection Device 0V V npn sink high speed counter frequency measurer pnp source high speed counter frequency measurer 0V V Circuit Protection Device High speed Counter Reset High speed Counter 0V V High speed Counter Reset High speed Counter ...

Page 6: ...ormity to voltage power supply specifications connect the device to a regulated power supply Notes 1 The adapter and output s power supply must be connected to the same 0V signal Outputs Circuit Protection Device L1 L2 L3 115 230VAC V 12 24VDC Output s power supply 0V V N 0V Load See Note 1 Increasing Contact Life Span Both modules have 8 relay outputs To increase the life span of these contacts a...

Page 7: ...Logic 0 0 3VDC 4 3mA for Logic 1 Input current 6mA 24VDC 6mA 12VDC Response time 10mSec typical Input 7 The specifications below apply when this input is wired for use as a high speed counter input frequency measurer See Notes 2 and 3 Resolution 16 bit Frequency 5kHz maximum Minimum pulse width 80µs Outputs Number of outputs 8 relay Output type SPST NO Form A All relays share a common signal Isola...

Page 8: ... number indicates the I O s location in the system This number relates to both the position of the expansion module in the system and to the position of the I O on that module Expansion modules are numbered from 0 7 as shown in the figure below 0 1 2 3 4 5 6 7 Expansion module identification number Adapter The formula below is used to assign addresses for I O modules used in conjunction with the O...