I/O Expansion Module           8 Relay Outputs 

The IO-RO8 and IO-RO8L are I/O 
expansion modules that can be used in 
conjunction with specific Unitronics OPLC 
controllers. 
The modules are identical except for their 
power supply specifications: IO-RO8 runs 
at 24 VDC; IO-RO8L at 12 VDC. 
Both modules offer 8 relay outputs. 
The interface between module and OPLC 
is provided by an adapter. 
These modules may either be snap-
mounted on a DIN rail, or screw-mounted 
onto a mounting plate.

 

Component identification 

Module-to-module connector 

Communication status indicator 

Outputs’ power supply  
connection points 

Output connection points: O4-O7 

Output’s status indicators 

Module-to-module connector port 

Output connection points: O0-O3 

 

 

1

6

2

3

4

7

5

POWER

 

User safety and equipment protection guidelines 

This document is intended to aid trained and competent personnel in the installation of this equipment as defined 
by the European directives for machinery, low voltage and EMC. Only a technician or engineer trained in the 
local and national electrical standards should perform tasks associated with the electrical wiring of this device. 

 

Under no circumstances will Unitronics be liable or responsible for any consequential damage that may 
arise as a result of installation or use of this equipment, and is not responsible for problems resulting from 
improper or irresponsible use of this device. 

 

All examples and diagrams shown in the manual are intended to aid understanding.  They do not  
guarantee operation. 

 

Unitronics accepts no responsibility for actual use of this product based on these examples. 

 

Only qualified service personnel should open this device or carry out repairs. 

 

Please dispose of this product in accordance with local and national standards and regulations. 

 

 

Check the user program before running it. 

 

Do not attempt to use this device with voltage exceeding permissible levels. 

 

Install an external circuit breaker and take appropriate safety measures against short-circuiting 
in external wiring. 

 

 

 

 

Failure to comply with appropriate safety guidelines can result in severe personal injury or 
property damage. Always exercise proper caution when working with electrical equipment. 

 

 

 

Summary of Contents for IO-RO8

Page 1: ... and EMC Only a technician or engineer trained in the local and national electrical standards should perform tasks associated with the electrical wiring of this device Under no circumstances will Unitronics be liable or responsible for any consequential damage that may arise as a result of installation or use of this equipment and is not responsible for problems resulting from improper or irrespon...

Page 2: ... a minimum space of 10mm between the top and bottom edges of the device and the enclosure walls Do not place in water or let water leak onto the unit Do not allow debris to fall inside the unit during installation DIN rail mounting Snap the device onto the DIN rail as shown below the module will be squarely situated on the DIN rail 60mm 3 5mm 14mm 80mm 93mm 44 5mm POWER Screw Mounting The figure o...

Page 3: ...12 01 IO RO8 IO RO8L I O Expansion Module Unitronics Industrial Automation Systems 3 4mm 5 8mm 85mm 80mm 68 4mm 93mm 4mm x2 ...

Page 4: ...st be connected to the same 0V signal Do not use tin solder or any other substance on the stripped wire that might cause the wire strand to break We recommend that you use crimp terminals for wiring Install at maximum distance from high voltage cables and power equipment General Wiring Procedures 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest positi...

Page 5: ...er supply specifications connect the device to a regulated power supply Load 0V N 0V N N 0V N 0V V 24VDC L1 L2 L3 115 230VAC Circuit Protection Device Load L1 L2 L3 115 230VAC V 24VDC 0V N 0V N N 0V N 0V Outputs power supply 0V V POWER Increasing Contact Life Span Both models have 8 relay outputs To increase the life span of these contacts and protect the module from potential damage by reverse EM...

Page 6: ... Isolation By relay Status Indicators O0 to O7 Red LEDs Lit when the corresponding output is active Output current 5A maximum resistive load 1A maximum inductive load Maximum frequency 10Hz Contact protection External precautions required see above Increasing Contact Life Span Outputs power supply IO RO8 Nominal operating voltage 24VDC Operating voltage 20 4 to 28 8VDC Maximum current consumption ...

Page 7: ...n module identification number Adapter The formula below is used to assign addresses for I O modules used in conjuction with the M90 OPLC X is the number representing a specific module s location 0 7 Y is the number of the input or output on that specific module 0 15 The number that represents the I O s location is equal to 32 x 16 y Examples Input 3 located on expansion module 2 in the system wil...

Page 8: ...IO RO8 IO RO8L I O Expansion Module 12 01 8 Unitronics Industrial Automation Systems ...