background image

JZ20-T40/JZ20-J-T40  

 

 

Unitronics 

 

 

   

Wiring Procedure 

Use crimp terminals for wiring; use 3.31 mm² –0.13 mm² wire (12-26 AWG): 

1. 

Strip the wire to a length of 7±0.5mm (0.270–0.300“). 

2. 

Unscrew the terminal to its widest position before inserting a wire.  

3. 

Insert the wire completely into the terminal to ensure a proper connection. 

4. 

Tighten enough to keep the wire from pulling free. 

Wiring Guidelines 

  Use separate wiring ducts for each of the following groups:  

  Group 1: Low voltage I/O and supply lines, communication lines.  

  Group 2: High voltage Lines, Low voltage noisy lines like motor driver outputs.  

Separate these groups by at least 10cm (4"). If this is not possible, cross the ducts at a 90˚angle. 

  For proper system operation, all 0V points in the system should be connected to the system 0V 

supply rail. 

Allow for voltage drop and noise interference with input lines used over an extended distance. Use 
wire that is properly sized for the load. 

Earthing the JZ20-T40/JZ20-J-T40 

To maximize system performance, avoid electromagnetic interference as follows: 

  Use a metal cabinet. 

    Connect the 0V terminal directly to the earth ground of the system. 

 

  Use the shortest, less than 1m (3.3 ft.) and thickest, 2.08mm² (14AWG) min, wires possible.

 

    

Inputs 

This model comprises a total of 20 inputs in 3 groups.  

1. 

I0 to I15 are digital inputs. They may be wired, in a group, as either npn or pnp.  

2. 

I16 and I17 may be wired as either digital or analog inputs. These may be wired as either: 

  npn digital inputs 

  pnp digital inputs 

  analog (voltage) inputs 

In addition, 1 input may be wired as a pnp input, while the other is wired as an analog input. 
Note that if 1 input is wired as an npn input, the other may not be wired as an analog input. 

3. 

AN0 and AN1 are analog (current) inputs that may be wired using 2, 3, or 4 wires. 

Summary of Contents for Jazz OPLC JZ20-T40

Page 1: ...ied service personnel should open this device or carry out repairs Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters that exceed permissible levels To avoid damaging the system do not connect disconnect the device when power is on Environmental Considerations Do not install in areas with excessive or co...

Page 2: ...agrams are based on the rear view of the OPLC This equipment is designed to operate only in SELV PELV Class 2 Limited Power environments All power supplies in the system must include double insulation Power supply outputs must be rated as SELV PELV Class 2 Limited Power Do not connect either the Neutral or Line signal of the 110 220VAC to device s 0V pin Do not touch live wires All wiring activiti...

Page 3: ...rail Allow for voltage drop and noise interference with input lines used over an extended distance Use wire that is properly sized for the load Earthing the JZ20 T40 JZ20 J T40 To maximize system performance avoid electromagnetic interference as follows Use a metal cabinet Connect the 0V terminal directly to the earth ground of the system Use the shortest less than 1m 3 3 ft and thickest 2 08mm 14...

Page 4: ... group as npn and the other as pnp or wire both groups as npn or as pnp In either case the n p pins must be connected Input wiring npn sink Input wiring pnp source Input wiring I0 I15 pnp source I16 I17 npn sink Digital Outputs Outputs Power Supply V01 is the power supply for outputs O0 O11 V02 is the power supply for outputs O12 O19 ...

Page 5: ...Shields should be connected at the signal source Analog Input wiring current AN0 AN1 2 or 3 wire 4 wire Analog Input wiring voltage AN2 AN3 Note If either I16 or I17 is wired as an npn digital input the remaining input may not be wired as an analog input ...

Page 6: ...mited to any implied warranties of merchantability fitness for a particular purpose or non infringement Unitronics assumes no responsibility for errors or omissions in the information presented in this document In no event shall Unitronics be liable for any special incidental indirect or consequential damages of any kind or any damages whatsoever arising out of or in connection with the use or per...

Reviews: