Vision™ OPLC™ V570-57-T20B, V570-57-T40B 

Installation Guide

 

 Unitronics 

 

 

Communication Ports 

This series comprises 2 RS232/RS485 serial ports and a CANbus port.  

 

ƒ

  Turn off power before making communications connections. 

Caution

 

ƒ

  Always use the appropriate port adapters. 

 

Serial Communications 

The serial ports are type RJ-11 and may be set to either RS232 or RS485 via DIP switches, in 
accordance with the table shown below. 
Use RS232 to download programs from a PC, and to communicate with serial devices and 
applications, such as SCADA.  
Use RS485 to create a multi-drop network containing up to 32 devices. 

Pinouts 

The pinouts below show PLC port signals. 
To connect a PC to a port that is set to RS485, remove the RS485 connector, and connect the PC to 
the PLC via the programming cable. Note that this is possible only if flow control signals are not used 
(which is the standard case). 

RS232  

RS485** 

Controller 

Port 

Pin # 

Description 

 

Pin # 

Description 

1* DTR 

signal 

 

1 A 

signal 

(+) 

2 0V 

reference 

 

2 (RS232 

signal) 

3 TXD 

signal 

 

3 (RS232 

signal) 

4 RXD 

signal 

 

4 (RS232 

signal) 

5 0V 

reference 

 

5 (RS232 

signal) 

6* DSR 

signal 

 

6 B 

signal 

(-) 

Pin #1

 

*Standard programming cables do not provide connection points for pins 1 and 6. 
**When a port is adapted to RS485, Pin 1 (DTR) is used for signal A,  
   and Pin 6 (DSR) signal is used for signal B. 

 

 

RS232 to RS485: Changing DIP Switch Settings 

The ports are set to RS232 by factory default. 
To change the settings, first remove the Snap-in I/O Module, if one is installed, and then set the 
switches according to the following table. 

 

RS232/RS485: DIP Switch Settings 

The settings below are for each COM port. 

 Switch 

Settings 

 

1 2 3 4 5 6 

RS232* ON 

ON 

ON 

OFF 

ON 

OFF 

RS485 

OFF OFF OFF 

ON 

OFF 

ON 

RS485 with 
termination** 

ON ON 

OFF 

ON 

OFF 

ON 

*Default factory setting

 

**Causes the unit to function as an end unit in an RS485 network

 

 

Summary of Contents for V570-57-T20B

Page 1: ...a adaptor local or remote I Os may be added via expansion port or CANbus Installation instructions and other data may be found in the module s technical specification sheet Information Mode This mode enables you to Calibrate the touchscreen View Edit operand values COM port settings RTC and screen contrast brightness settings Stop initialize and reset the PLC To enter Information Mode press the to...

Page 2: ...ntified danger causes physical and property damage Warning The identified danger could cause physical and property damage Caution Caution Use caution Before using this product the user must read and understand this document All examples and diagrams are intended to aid understanding and do not guarantee operation Unitronics accepts no responsibility for actual use of this product based on these ex...

Page 3: ...ttery The battery is supplied taped to the battery cover on the rear of the controller 1 Remove the battery cover shown on page 4 The polarity is marked on the battery holder and on the battery 2 Insert the battery ensuring that the polarity symbol on the battery is facing up aligned with the symbol on the holder 3 Replace the battery cover Mounting Dimensions ...

Page 4: ...re to the right 2 Slide the controller into the cut out ensuring that the rubber seal is in place 3 Push the 4 mounting brackets into their slots on the sides of the controller as shown in the figure to the right 4 Tighten the bracket screws against the panel Hold the bracket securely against the unit while tightening the screw 5 When properly mounted the controller is squarely situated in the pan...

Page 5: ...ply The permissible input voltage range is 20 4 28 8VDC with less than 10 ripple A non isolated power supply can be used if a 0V signal is connected to the chassis Install an external circuit breaker Guard against short circuiting in external wiring Double check all wiring before turning on the power supply Do not connect either the Neutral or Line signal of the 110 220VAC to device s 0V pin In th...

Page 6: ...le only if flow control signals are not used which is the standard case RS232 RS485 Controller Port Pin Description Pin Description 1 DTR signal 1 A signal 2 0V reference 2 RS232 signal 3 TXD signal 3 RS232 signal 4 RXD signal 4 RS232 signal 5 0V reference 5 RS232 signal 6 DSR signal 6 B signal Pin 1 Standard programming cables do not provide connection points for pins 1 and 6 When a port is adapt...

Page 7: ...n to open the locking mechanism 3 Gently rock the module from side to side easing the module from the controller Re installing a Snap in I O Module 1 Line the circular guidelines on the controller up with the guidelines on the Snap in I O Module as shown below 2 Apply even pressure on all 4 corners until you hear a distinct click The module is now installed Check that all sides and corners are cor...

Page 8: ...g Unitronics reserves the right subject to all applicable laws at any time at its sole discretion and without notice to discontinue or change the features designs materials and other specifications of its products and to either permanently or temporarily withdraw any of the forgoing from the market All information in this document is provided as is without warranty of any kind either expressed or ...

Reviews: