background image

Vision™ OPLC™  

Unitronics  

5

Power Supply 

The controller requires an external 12VDC or 24VDC power supply. 

 

A non-isolated power supply can be used if a 0V signal is connected to the chassis. 

Install an external circuit breaker. Guard against short-
circuiting in external wiring. 

Double-check all wiring before turning on the  
power supply. 

Do not connect either the ‘Neutral or ‘Line’ signal of the 
110/220VAC to device’s 0V pin. 

In the event of voltage fluctuations or non-conformity to 
voltage power supply specifications, connect the device 
to a regulated power supply. 

Earthing the Power Supply 

To maximize system performance, avoid electromagnetic interference by: 

Mounting the controller on a metal panel. 

Earthing the controller’s power supply: connect one end of a 14 AWG wire to the chassis 
signal; connect the other end to the panel. 

Note: If possible, the wire used to earth the power supply should not exceed 10 cm in length. 
However, it is recommended to earth the controller in all cases. 

 

Communication Port 

 

Turn off power before making communications connections. 

Caution

 

Signals are related to the controller’s 0V; the same 0V is used by the power supply. 

Always use the appropriate port adapters. 

The serial port is not isolated. If the controller is used with a non-isolated external 
device, avoid potential voltage that exceeds ± 10V. 

Port 1 is type RJ-11 and may be set to either RS232 or RS485 via jumper as shown below.  
By factory default, the port is set to RS232, termination ON. 

Use RS232 to download programs from a PC, and to communicate with serial devices 
and applications, such as SCADA. 

Use RS485 to create a multi-drop network containing up to 32 devices. 

 

Summary of Contents for Vision OPLC V130-33-B1

Page 1: ...his mode enables you to View Edit operand values COM port settings RTC and screen contrast brightness settings Stop initialize and reset the PLC To enter Information Mode press the i button for several seconds Programming Software Utilities The Unitronics Setup CD contains VisiLogic software and other utilities VisiLogic Easily configure hardware and write both HMI and Ladder control applications ...

Page 2: ...onics accepts no responsibility for actual use of this product based on these examples Please dispose of this product according to local and national standards and regulations Only qualified service personnel should open this device or carry out repairs Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters ...

Page 3: ...ller into the cut out ensuring that the rubber seal is in place 3 Push the 2 mounting brackets into their slots on the sides of the controller as shown in the figure to the right 4 Tighten the bracket screws against the panel Hold the bracket securely against the unit while tightening the screw 5 When properly mounted the controller is squarely situated in the panel cut out as shown in the figure ...

Page 4: ... kgf cm Do not use tin solder or any substance on stripped wire that might cause the wire strand to break Install at maximum distance from high voltage cables and power equipment Wiring Procedure Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm 2 3 31 mm2 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Inse...

Page 5: ...wer supply connect one end of a 14 AWG wire to the chassis signal connect the other end to the panel Note If possible the wire used to earth the power supply should not exceed 10 cm in length However it is recommended to earth the controller in all cases Communication Port Turn off power before making communications connections Caution Signals are related to the controller s 0V the same 0V is used...

Page 6: ...gnal 4 RS232 signal 5 0V reference 5 RS232 signal 6 DSR signal 6 B signal Pin 1 Standard programming cables do not provide connection points for pins 1 and 6 When a port is adapted to RS485 Pin 1 DTR is used for signal A and Pin 6 DSR signal is used for signal B RS232 to RS485 Jumper Settings The figure to the right shows the jumper factory default settings RS232 RS485 termination ON Note that in ...

Page 7: ...ntroller 1 Gently replace the board Make certain that the pins fit correctly into their matching receptacle Do not force the board into place doing so may damage the controller 2 Replace the back cover of the controller and fasten the corner screws Note You must replace the back cover securely before powering up the controller Samara tel 7 846 273 95 85 samara klinkmann spb ru Yekaterinburg tel 7 ...

Reviews: