background image

Unitronics  

Vision™ OPLC™ 

V130-33-R2 Installation Guide 
12 pnp/npn Digital, including 2 Analog, 3 HSC/Shaft-
encoder Inputs, 6 Relay Outputs

 

This guide provides basic information for Unitronics’ controller model V130-33-R2.   

General Description 

V130 OPLCs are micro-OPLCs, rugged programmable logic controllers that comprise:  

On-board I/O configuration 
Built-in operating panel containing an LCD and a keypad  

Communications 

1 built-in serial port: RS232/RS485  
Optional: the user may order and install 
one or both of the following modules:  
- RS232/RS485/Ethernet  
- CANbus  
Communication Function Blocks include: 
SMS, GPRS, MODBUS serial/IP. Protocol 
FB enables PLC to communicate with 
almost any external device, via serial or 
Ethernet communications 

I/O Options 

V130 supports digital, high-speed, analog, 
and temperature measurement I/Os via: 

On-board I/O configuration
Model-dependent 
I/O Expansion Modules
Via adaptor, use up to 8 I/O Expansion 
Modules, add up to 128 additional I/Os 

Information Mode 

This mode enables you to: 

View & Edit operand values, COM port settings, RTC and screen 
contrast/brightness settings 
Stop, initialize, and reset the PLC 

To enter Information Mode, press the <i> button for several seconds. 

Programming 
Software,  
& Utilities 

The Unitronics Setup CD contains VisiLogic software and other utilities 

VisiLogic
Easily configure hardware and write both HMI and Ladder control 
applications; the Function Block library simplifies complex tasks 
such as PID. Write your application, and then download it to the 
controller via the programming cable included in the kit. 
Utilities
Includes UniOPC server, Remote Access for remote programming 
and diagnostics, and DataXport for run-time data logging. 

To learn how to use and program the controller, as well as use utilities such 
as Remote Access, refer to the VisiLogic Help system. 

Data Tables 

120K dynamic data (recipe parameters, datalogs, etc.),  
192K fixed data (read-only data, ingredient names, etc) 

Additional product documentation is in the Technical Library, located at 

www.unitronics.com

, and on 

the Unitronics’ Setup CD. 
Technical support is available at the site, and from support@unitronics.com. 

 

Summary of Contents for Vision OPLC V130-33-R2

Page 1: ...s Information Mode This mode enables you to View Edit operand values COM port settings RTC and screen contrast brightness settings Stop initialize and reset the PLC To enter Information Mode press the i button for several seconds Programming Software Utilities The Unitronics Setup CD contains VisiLogic software and other utilities VisiLogic Easily configure hardware and write both HMI and Ladder c...

Page 2: ... of this product according to local and national standards and regulations Only qualified service personnel should open this device or carry out repairs Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters that exceed permissible levels To avoid damaging the system do not connect disconnect the device when...

Page 3: ...oller into the cut out ensuring that the rubber seal is in place 3 Push the 2 mounting brackets into their slots on the sides of the controller as shown in the figure to the right 4 Tighten the bracket screws against the panel Hold the bracket securely against the unit while tightening the screw 5 When properly mounted the controller is squarely situated in the panel cut out as shown in the figure...

Page 4: ... m 5 kgf cm Do not use tin solder or any substance on stripped wire that might cause the wire strand to break Install at maximum distance from high voltage cables and power equipment Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm 2 3 31 mm2 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Insert the wire c...

Page 5: ...5 can function as either counter reset as normal digital inputs or as part of a shaft encoder Input Jumper Settings The tables below show how to set a specific jumper to change input functionality To access the I O jumpers you must open the controller according to the instructions beginning on page 9 Incompatible jumper settings and wiring connections may seriously damage the controller Do not mov...

Page 6: ...p source HSC input wiring npn sink HSC input wiring pnp source Shaft encoder Analog input wiring voltage current 4 wire Analog input wiring current 2 3 wire Shields should be connected at the signal s source The 0V signal of the analog input must be connected to the controller s 0V ...

Page 7: ...ard against short circuiting in external wiring Double check all wiring before turning on the power supply Do not connect either the Neutral or Line signal of the 110 220VAC to device s 0V pin In the event of voltage fluctuations or non conformity to voltage power supply specifications connect the device to a regulated power supply Earthing the Power Supply To maximize system performance avoid ele...

Page 8: ...S485 remove the RS485 connector and connect the PC to the PLC via the programming cable Note that this is possible only if flow control signals are not used which is the standard case RS232 RS485 Controller Port Pin Description Pin Description 1 DTR signal 1 A signal 2 0V reference 2 RS232 signal 3 TXD signal 3 RS232 signal 4 RXD signal 4 RS232 signal 5 0V reference 5 RS232 signal 6 DSR signal 6 B...

Page 9: ...the controller comprises 4 screws located in the corners Remove the screws and pull off the back cover Changing I O settings 1 The I O board of the controller is now exposed enabling you to change I O settings according to the jumpers shown on page 5 Changing Communication settings 1 To access the communication jumpers hold the I O PCB board by its top and bottom connectors and steadily pull the b...

Page 10: ...rarily withdraw any of the forgoing from the market All information in this document is provided as is without warranty of any kind either expressed or implied including but not limited to any implied warranties of merchantability fitness for a particular purpose or non infringement Unitronics assumes no responsibility for errors or omissions in the information presented in this document In no eve...

Reviews: