Goodrive10 inverters Product overview
9
2.2 Product specification
Function
Specification
Power input
Input voltage (V)
Single-phase 220(-15%)~240(+10%)
Three-phase 220(-15%)~240(+10%)
Three-phase 380(-15%)~440(+10%)
Input current (A)
Refer to 2.5
Input frequency (Hz)
50Hz or 60Hz Allowed range: 47~63Hz
Power
output
Output voltage (V)
=the input voltage (error
<
5%)
Output current (A)
Refer to 2.5
Output power (kW)
Refer to 2.5
Output frequency (Hz)
50Hz/60Hz, fluctuation:±5%
Technical
control
Control mode
SVPWM
Maximum output
frequency
400Hz
Adjustable-speed ratio
1:100
Overload capability
150% of rated current: 1 minute
180% of rated current: 10 seconds
200% of rated current: 1 second
Running
control
Key functions
Stop mode and anti-overtemperature of the bus
Temperature
measurement accuracy
Overtemperature point ±3
℃
Terminal switch input
resolution
≤ 2ms
Terminal analog input
resolution
≤ 20mV
Analog input
1 input 0~10V/0~20mA
Analog output
1 output 0~10V/0~20mA
Digital input
5 common input
Digital output
1 Y output (commonly used with digital output) and 1
pogrammable relay output
Communication
485 communication
Frequency setting
Digital setting, analog setting, multi-step speed setting,
PID setting, MODBUS communication setting and so on
Switch between different settings
Automatic voltage
adjustment
Keep output voltage stable when the grid voltage changes