Goodrive10 inverters Appendix C
103
The inverter
Fuse (A)
Breaker (A)
The rated working current
of the contactor
(A)
GD10-0R4G-S2-B
16
16
10
GD10-0R7G-S2-B
16
16
16
GD10-1R5G-S2-B
25
25
16
GD10-2R2G-S2-B
50
40
32
GD10-0R2G-2-B
6
6
6
GD10-0R4G-2-B
6
10
10
GD10-0R7G-2-B
10
10
10
GD10-1R5G-2-B
25
16
16
GD10-2R2G-2-B
32
25
16
GD10-0R7G-4-B
10
6
10
GD10-1R5G-4-B
10
10
10
GD10-2R2G-4-B
16
16
10
C.5 Reactors
High current in the input power circuit may cause damage to the rectifying components. It is appropriate to
use AC reactor in the input side for the avoidance of high-voltage input of the power supply and improvement
of the power factors.
If the distance between the inverter and the motor is longer than 50m, frequent overcurrent protection may
occur to the inverter because of high leakage current caused by parasitic capacitance effects from the long
cables to the ground. In order to avoid the damage of the motor insulation, it is necessary to add reactor
compensation.