Goodrive10 inverters Function codes
33
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
The setting range of P01.09: 0.00Hz~P00.03
The setting range of P01.10: 0.0~50.0s
The setting range of P01.11: 0.0~100.0%
The setting range of P01.12: 0.0~50.0s
P01.13
Dead time of
FWD/REV
rotation
During the procedure of switching FWD/REV rotation, set
the threshold by P01.14, which is as the table below:
Setting range: 0.0~3600.0s
0.00s
○
P01.14
Switching
between
FWD/REV
rotation
Set the threshold point of the inverter:
0: Switch after 0 frequency
1: Switch after the starting frequency
2: Switch after a delay time when the inverter stops
0
◎
P01.15
Stopping
speed
0.00~100.00Hz
1.00 Hz
◎
P01.18
Terminal
running
protection
when
powering on
When the running command channel is the terminal control,
the system will detect the state of the running terminal
during powering on.
0: The terminal running command is invalid when powering
on. Even the running command is detected to be valid
during powering on, the inverter won’t run and the system
0
○