Goodrive10 inverters Function codes
39
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
Of which, f
b
is the rated frequency of the motor, its function
code is P02.02; n is the rated rotating speed of the motor
and its function code is P02.03; p is the pole pair of the
motor. 100.0% corresponds to the rated slip frequency
△
f.
Note: no torque compensation for single-phase 220V
inverters
Setting range:0.0~200.0%
220V:0%
P04.10
Low frequency
vibration
control factor
In the SVPWM control mode, current fluctuation may occur
to the motor on some frequency, especially the motor with
big power. The motor can not run stably or overcurrent may
occur. These phenomena can be canceled by adjusting this
parameter.
The setting range of P04.10: 0~100
The setting range of P04.11: 0~100
The setting range of P04.12:0.00Hz~P00.03(the Max.
frequency)
10
○
P04.11
High
frequency
vibration
control factor
10
○
P04.12
Vibration
control
threshold
30.00 Hz
○
P04.26
Eneregy-savin
g operation
0: No operation
1: Automatic eneergy-saving
The motor adjust the output voltage in non-load state
automatically.
0
◎
P05 Group Input terminals
P05.01
S1 terminals
function
selection
0: No function
1: Forward rotation operation
2: Reverse rotation operation
3: 3-wire control operation
4: Forward rotation jogging
5: Reverse rotation jogging
6: Coast to stop
7: Fault reset
8: Operation pause
9: External fault input
10:Increasing frequency setting(UP)
1
◎
P05.02
S2 terminals
function
selection
4
◎
P05.03
S3 terminals
function
selection
7
◎