Goodrive10 inverters Function codes
41
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
1:MODBUS communication virtual terminals are valid
P05.13
Terminals
control running
mode
Set the operation mode of the terminals control
0:2-wire control 1, comply the enable with the direction.
This mode is widely used. It determines the rotation
direction by the defined FWD and REV terminals
command.
1:2-wire control 2
;
Separate the enable from the direction.
FWD defined by this mode is the enabling ones. The
direction depends on the state of the defined REV.
2:3-wire control 1; Sin is the enabling terminal in this mode,
and the running command is caused by FWD and the
direction is controlled by REV. Sin is natural closed.
3:3-wire control 2; Sin is the enabling terminal on this mode,
if set Si (i=1~5) to 3, when K is switched on, the control of
FWD and REV is valid; when K is switched off, the control
of FWD and REV is invalid. The inverter stops.
Note: for the 2-wire running mode, when FWD/REV
terminal is valid, the inverter stop because of the stopping
command from other sources, even the control terminal
FWD/REV keeps valid
; the inverter won’t work when the
stopping command is canceled. Only when FWD/REV is
relaunched, the inverter can start again.
0
◎
P05.14
S1 terminal
switching on
delay time
The function code defines the corresponding delay time of
electrical level of the programmable terminals from
switching on to switching off.
Setting range:0.000~50.000s
0.000s
○
P05.15
S1
terminal
switching off
delay time
0.000s
○
P05.16
S2 terminal
switching on
delay time
0.000s
○
P05.17
S2
terminal
switching off
0.000s
○