Goodrive10 inverters Function codes
56
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
voltage
220V
380V
range
3755~400V
685~750V
P08.39
Cooling fan
running mode
0:Rated running mode
1:The fan keeps on running after power on
0
○
P08.40 PWM selection
0x0000~0x0021
LED ones: PWM mode selection
0: PWM mode 1, Three-phase modulation and two-phase
modulation
1: PWM mode 2, Three-phase modulation
LED tens: low-speed carrier frequency limit
0: low-speed carrier frequency limit mode 1; when the
carrier frequency exceeds 1k at low speed, limit to 1k.
1: low-speed carrier frequency limit mode 2; when the
carrier frequency exceeds 2k at low speed, limit to 2k.
2: No limt for the carrier frequency at low speed
0x01
◎
P08.41
Over
commission
selection
0:Invalid
1:Valid
1
◎
P08.42
Keypad data
control setting
0x000~0x1223
LED ones: frequency enable selection
0:
∧
/
∨
keys adjustments are valid
1: Reserved
2:
∧
/
∨
keys adjustments are invalid
3: Reserved
LED tens: frequency control selection
0: Only valid when P00.06=0 or P00.07=0
1: Valid for all frequency setting manner
2: Invalid for multi-stage speed when multi-stage speed has
the priority
LED hundreds: action selection during stopping
0: Setting is valid
1: Valid during running, cleared after stopping
2: Valid during running, cleared after receiving the stop
command
LED thousands:
∧
/
∨
keys and digital potentiometer
Integral function
0: The Integral function is valid
1: The Integral function is invalid
0x0000
○