Goodrive10 inverters Appendix A
95
Appendix A Technical data
A.1 Ratings
A.1.1 Capacity
Inverter sizing is based on the rated motor current and power. To achieve the rated motor power reference in
the table, the rated current of the inverter must be higher than or equal to the rated motor current. Also the
rated power of the inverter must be higher than or equal to the rated motor power. The power ratings are the
same regardless of the supply voltage within one voltage range.
Note:
1.
The maximum allowed motor shaft power is limited to 1.5*PN. If the limit is exceeded, motor torque and
current are automatically restricted. The function protects the input bridge of the drive against overload.
2.
The ratings apply at ambient temperature of 40 °C
3.
It is important to check that in Common DC systems the power flowing through the common DC
connection does not exceed PN.
A.1.2 Derating
The load capacity decreases if the installation site ambient temperature exceeds 40 °C, the altitude exceeds
1000 meters or the switching frequency is changed from 4 kHz to 8, 12 or 15 kHz.
A.1.2.1 Temperature derating
In the temperature range +40 °C~+50 °C, the rated output current is decreased by 3% for every additional
1 °C. Refer to the below list for the actual derating.
A.1.2.2 Altitude derating
The device can output at rated power if the installation site below 1000m. The output power decreases if the
altitude exceeds 1000 meters. Below is the detailed decreasing range of the derating: