1.0
Safety
• Clearance to Combustibles
Chart 1.1 •
Clearance to Combustibles in Inches
(see Figure 1.1 for Mounting Angles)
The stated clearance to combustibles represents a surface temperature of 90°F (32°C) above room
temperature. Building materials with a low heat tolerance (such as plastics, vinyl siding, canvas,
tri-ply, etc.) may be subject to degradation at lower temperatures. It is the installer’s responsibility to
assure that adjacent materials are protected from degradation.
Figure 1.1
•
Mounting Angles
*
Heaters mounted on an angle between 0° to 45° must maintain clearances posted for 0° or 45°; whichever is greater.
45° Mounting Angle
0° Mounting Angle
with 1 Side Shield
(P/N: SSE)
0° Mounting Angle
with 2 Side Shields
(P/N: SSE)
Front
Behind
Below
Top
Front
Behind
Below
Top
Side
Side
Below
Top
0° Mounting Angle
Side
Side
Below
Top
Model Number
Mounting
Angle*
Side
Top
Below
Front
Behind
RHT-(65, 75)[N, P]-(20, 30, 40)
0°
9
9
6
60
45°
39
8
10
60
with 1 side shield
0°
29
8
6
60
with 2 side shields
0°
9
9
6
60
20 ft. from burner
0°
7
7
6
30
RHT-100[N, P]-(30, 40)
0°
14
14
6
66
45°
39
8
10
66
with 1 side shield
0°
29
8
6
66
with 2 side shields
0°
16
16
6
66
20 ft. from burner
0°
7
7
6
30
RHT-125[N, P]-(40, 50)
0°
20
20
6
76
45°
58
8
10
76
with 1 side shield
0°
42
8
6
76
with 2 side shields
0°
20
20
6
76
20 ft. from burner
0°
7
7
6
30
RHT-150[N, P]-(40, 50, 60)
0°
24
24
6
81
45°
58
8
10
81
with 1 side shield
0°
42
8
6
81
with 2 side shields
0°
23
23
6
81
20 ft. from burner
0°
11
11
6
44
RHT-175[N, P]-(50, 60)
0°
34
34
6
92
45°
63
8
10
92
with 1 side shield
0°
50
8
6
92
with 2 side shields
0°
30
30
6
92
20 ft. from burner
0°
11
11
6
44
RHT-200[N, P]-(50, 60)
0°
41
41
6
94
45°
63
8
10
94
with 1 side shield
0°
54
8
6
94
with 2 side shields
0°
30
30
6
94
20 ft. from burner
0°
11
11
6
44