background image

3267 Grapevine St | Mira Loma, CA 91752 | 

T: 

(888) 866-4765 | 

F: 

(888) 866-

4765 

 

 

 

CONNECT SECONDARY WIRES TO TRANSFORMER

 

 

1.

 

Remove the bottom plate from the transformer. 

2.

 

Using a flathead screwdriver, adjust the common tap and appropriate low voltage tap on 
terminal lug to accept secondary wires. 

3.

 

Run the secondary wire cables through the knockouts in the bottom plate. 

4.

 

Separate the wires from each pair and strip both approximately one inch. 

5.

 

Connect one wire from each pair to the common tap and the other wire to the appropriate low 
voltage tap. 

6.

 

Secure the wires to the taps by tightening the common tap and the low voltage taps with a 
flathead screwdriver. 

 

CHECK VOLTAGE AT EACH FIXTURE

 

 

It is very important that the secondary voltage provided to each fixture is within the input voltage range 
of the lamp or fixture. Halogen lamps and some LEDs have an input voltage rating of 12V. If the specified 
input voltage range is 12V, the input voltage provided to the fixture must be between 11V and 12V. If the 
voltage at the socket exceeds 12V, light output of the lamp will be higher but average rated life will 
be lower. If the voltage at the socket is lower than 11V, light output will be lower and average rated life 
will be higher. Many LEDs have an input voltage range of 10V - 15V, or 10V - 18V. For LEDs with input 
voltage ranges, input voltage supplied to the lamp within that range is acceptable. 

 

 

1.

 

Plug the transformer into a covered 120V GFCI receptacle. 

2.

 

Switch on the transformer to provide secondary voltage to the fixtures. 

3.

 

Using a voltmeter, check the voltage at each fixture. 

4.

 

Make sure that the voltage at each fixture is within the specified input voltage range of the 
lamps or integrated LED fixtures. 

5.

 

If the measured voltage falls outside of the specified input voltage range of the lamps or 
integrated LED fixtures, adjust the voltage to the acceptable range by moving the wire to 
higher/lower voltage tap. 

 
 

CHECK OUTPUT AMPS

 

 

After checking the voltages on the run, use a clamp-on meter to measure the output current on the low 
voltage cable at the transformer for each circuit. Make sure that the output current of the circuit is 
below the maximum rated Amperage. 

 

 

Circuit Size 

50 Watts 

100 Watts 

150 Watts 

Amp Rating 

4.166A 

8.33A 

12.5A 

Summary of Contents for ECO Series

Page 1: ...OT USE AN EXTENSION CORD WITH THIS POWER SUPPLY Sizing Transformer The total wattage W or volt amps VA for LED of all of the fixtures operated by this transformer must not exceed the wattage rating of the transformer If you are powering halogen lamps calculate the load by adding the wattage of the lamps in the system Make sure the load does not exceed the wattage rating of the transformer If you a...

Page 2: ...transformer with a maximum wattage rating of 150W can be utilized MOUNT THETRANSFORMER UNIT 1 Remove transformer door for easy access 2 Find a solid flat surface to mount the transformer in a location a That is at least 12 inches between the terminals and ground level with wire terminals facing down and b Six feet or fewer from a 120V supply circuit that is protected by a Class A type ground fault...

Page 3: ...t exceeds 12V light output of the lamp will be higher but average rated life will be lower If the voltage at the socket is lower than 11V light output will be lower and average rated life will be higher Many LEDs have an input voltage range of 10V 15V or 10V 18V For LEDs with input voltage ranges input voltage supplied to the lamp within that range is acceptable 1 Plug the transformer into a cover...

Page 4: ...Below is a table that lists the cable constant value of different wire gauges Wire Gauge 18 2 16 2 14 2 12 2 10 2 8 2 Cable Constant 1 380 2 200 3 500 7 500 11 920 18 960 Example A 75 ft run with 100W load using 12 2 wire Voltage Drop 75 x 100 x 2 7500 2V This means that a 14V tap is needed to deliver 12V to the final fixture on the run One way to minimize voltage drop in this example is to spread...

Page 5: ...cuit 3 Reset Button Photocell Digital Display Screen Upand Down Arrow Button 4 To Operate Timer a Off No display b On 0 always ON c Auto A On at Dusk Off at Dawn d 1 2 3 4 5 6 7 8 9 On at Dusk Off at 1 2 3 4 5 6 7 8 9 Hrs 1 Timer will stop and reset if unit is exposed to 30sec of light during countdown 2 After full countdown is completed unit will reset only after 1 hours of exposure to lights Not...

Reviews: