background image

 10. Close (A) Low Side and (B) High Side manifold valves.

 11. Disconnect (C) Blue EZ Turn Hose from refrigerant cylinder.

 12. Disconnect (E) Red EZ Turn Hose from (C) Blue Hose EZ Access “T” fitting.

 13. The hoses have now been purged of non-condensable gases with the 

        refrigerant needed for service.

USER MANUAL - PART# USMAN5

Uniweld SmarTech Wireless Digital Manifold

 

FOR USE BY PROFESSIONALS. This manifold is designed for use by technically

trained refrigeration and air conditioning service technicians, due to the 

unusually HIGH PRESSURE AND HAZARDOUS GASES IN ALL SYSTEMS

misapplication could result in injury or death. The manufacturer warns 

against the sale of this product to, or its use by, other than professional 

trained personnel.

    WARNING: Read carefully and completely before using equipment. 

Keep for reference and store in back of protective case.

    WARNING: Always wear safety goggles when working with refrigerants.

    WARNING: CALIFORNIA PROPOSITION 65: This product contains chemicals

known to the State of California to cause cancer and birth defects or other 

reproductive harm

Package Contents

 1. SmarTech Wireless Digital Manifold w/ Rubber Boot

 2. (1) Blue and (1) Red Temperature Clamp K-Type with 6 Ft. lead

 3. (2) Thermocouple Bead Probes K-Type

 4. (1) Red 5 Ft. EZ Turn® Anti-Blowback Hose 

 5. (1) Blue 5 Ft. EZ Turn® Anti-Blowback Hose with 1/4” EZ Access “T” Fitting™

 6. (1) Black 5 Ft. Fast-Flo 3/8” Vacuum & Charging Hose with Ball Valve

 7. (1) Adaptor 3/8” MF x 1/4” FF

 8. SmarTech Protective Padded Case

 9. (6) AA Batteries (not shown)

 10. (10) Velcro Cable Tie Straps

OI0047

!

!
!

The SmarTech Digital Manifold is extremely accurate and can be used to pressure 

test the hoses and manifold valves for leaks. Note: The POE oil used in R410A is very 

aggressive and causes the rubber seals in the hoses and manifold valve stems to 

wear rapidly; they may need replacing every couple of months depending on usage. 

It is recommended to check your manifold and hoses regularly for leaks due to 

normal wear on rubber gaskets and seats.  

1. Connect (C) Blue EZ Turn Hose to manifold 45º hose holder fitting.

2. Connect (E) Red EZ Turn Hose to manifold 45º hose holder fitting.

3. Connect (D) Black 3/8” Hose with Ball Valve open to nitrogen regulator 

     using the 3/8”x1/4” adaptor.

4. Open (A) Low Side and (B) High Side manifold valves.

5. Open nitrogen tank valve and set delivery pressure between 400 to 500 psi.

6. Close (D) Black 3/8” Hose Ball Valve. A slight pressure drop is normal as the hoses     

     stretch under pressure but will stabilize after a couple of minutes.

7. Close (A) Low Side and (B) High Side manifold valves.

8. If digital pressure readings are stable the hoses and manifold are 

     functioning properly.

9. If the pressure reading continues to decrease there is a leak in the hoses or    

     manifold that must be repaired. Determine origin of the leak and replace    

     the gaskets and O-rings as needed. Repeat pressure test.

Manifold and Hoses Leak Test 

    Prior to purging the hoses with the refrigerant needed for service it may be    

    necessary to discharge unwanted refrigerant or nitrogen from the hoses. 

 1. Open (A) Low Side and (B) High Side manifold valves.

 2. Aim the (D) Black 3/8” Hose Ball Valve in a safe direction and open 

        the ball valve to discharge the unwanted refrigerant or nitrogen from the hoses.

 3. The digital pressure readings for both Hi and Lo should read zero before 

        continuing to the next step of purging the hoses with refrigerant. 

 4. Connect (E) Red EZ Turn Hose to (T) Blue Hose EZ Access “T” fitting.

 5. Connect (C) Blue EZ Turn Hose to refrigerant cylinder.

 6. Close (D) Black 3/8” Hose Ball Valve.

 7. Open refrigerant cylinder valve.

 8. Aim the (D) Black 3/8” Hose Ball Valve in a safe direction, open ball valve 

         and begin purging non-condensable gases.

 9. Close (D) Black 3/8” Hose Ball Valve when all non-condensable gases have 

        been purged.

  The SmarTech Digital Manifold is extremely accurate and can be used to 

  pressure test the system for leaks. Prior to pressure testing with nitrogen it 

  may be necessary to discharge unwanted refrigerant from the hoses.

 1. Open (A) Low Side and (B) High Side manifold valves.

 2. Aim the (D) Black 3/8” Hose Ball Valve in a safe direction and open 

         the ball valve to discharge the unwanted refrigerant from the hoses.

 3. The digital pressure readings for both Hi and Lo should read 

         zero before continuing to the next step.

 4. Connect (E) Red EZ Turn Hose to (F) High Side service fitting.

 5. Connect (C) Blue EZ Turn Hose to (G) Low Side service fitting.

 6. Connect (D) Black 3/8” Hose with Ball Valve open to nitrogen regulator 

         using the 3/8”x1/4” adaptor.

 7. Open nitrogen tank valve and set delivery pressure to system manufacturer’s     

          recommended test pressure.

 8. Close (D) Black 3/8” Hose Ball Valve. A slight pressure drop is normal as the

         hoses stretch under pressure but will stabilize after a couple of minutes.

 9. Close (A) Low Side and (B) High Side manifold valves.

 10. If after a few minutes the pressure reading continues to decrease there 

         is a system leak. The leak must be repaired then repeat the system 

         pressure test.

 11. If after a few minutes the digital pressure readings are stable the system is     

         leak-free.

 12. Close the nitrogen cylinder valve.

 13. Disconnect (D) Black 3/8” Hose from the nitrogen regulator.

 14. Open (A) Low Side and (B) High Side manifold valves.

 15. Aim the (D) Black 3/8” Hose Ball Valve in a safe direction and open 

         the ball valve to discharge the nitrogen from the system and hoses.

 16. Proceed with evacuating the system.

      Prior to charging a system with refrigerant the hoses must be evacuated or purged with      

       the refrigerant needed for service,  see Discharge and Purge Hoses before proceeding.

 1. 

Turn system off and connect (E) Red EZ Turn Hose to (F) High Side service fitting.

 2. 

Attach (H) Red Temperature Clamp to (F) High Side copper tubing.

 3. 

Connect (C) Blue EZ Turn Hose to (G) Low Side service fitting.

 4. Attach (J) Blue Temperature Clamp to (G) Low Side copper tubing.

 5. Connect (D) Black 3/8” Hose with Ball Valve closed to refrigerant cylinder.

 6. 

If this is a new system installation, open (F) High Side and (G) Low Side

               condenser service valves.

 7. 

Open (D) Black 3/8” Hose with Ball Valve and refrigerant cylinder valve.

 8. 

Turn system on; SmarTech Superheat and Subcooling features can be used at this time  

               to properly charge the system for maximum efficiency and optimal performance.

 9. 

To add refrigerant open (A) Low Side manifold valve.

 10. Close (A) Low Side manifold valve and let the system temperatures and pressures  

 

               stabilize. Check Superheat and Subcooling “Smart Charge Zone”, if additional  

 

               refrigerant is needed repeat steps 9 and 10 until the “Smart Charge Zone” is “Green” .

    11. Close (A) Low Side manifold valve when desired amount of refrigerant has 

               been added.

 12. 

Close (D) Black 3/8” Hose Ball Valve and refrigerant cylinder valve.

 13. Disconnect (D) Black 3/8” Hose with Ball Valve from refrigerant cylinder and 

              connect to manifold hose holder fitting.

 14. Disconnect (E) Red EZ Turn Hose and (C) Blue EZ Turn Hose from system and 

              connect to manifold hose holder fittings.

Prior to evacuating the system it may be necessary to discharge unwanted 

nitrogen or refrigerant from the hoses, see Discharge & Purge Hoses steps 1-2 

before proceeding.

1. Connect (E) Red EZ Turn Hose to (F) High Side service fitting.

2. Connect (C) Blue EZ Turn Hose to (G) Low Side service fitting.

3. Optional: Connect (Uniweld Part# UVG) Digital Vacuum Gauge 

     to (T) Blue Hose EZ Access “T” fitting. 

4. Open (A) Low Side and (B) High Side manifold valves.

5. Connect (D) Black 3/8” Hose with Ball Valve open to vacuum pump.

6. Evacuate system according to manufacturer’s specification.

7. Close (A) Low Side and (B) High Side manifold valves.

8. Close (D) Black 3/8” Hose Ball Valve and disconnect from the vacuum pump. 

9. Turn vacuum pump off and proceed with charging system with refrigerant.

A

A

C

T

C

E

E

A

B

B

B

D

D

MENU

PAIR

O

Enter

Right

––––

Hold

Left

––––

Max Min

Down

––––

Up

––––

+

  D i g i t a l   M a n i f o l d

A

C

E

D

B

LOW

HIGH

MENU

PAIR

O

Enter

Right

––––

Hold

Left

––––

Max Min

Down

––––

Up

––––

+

  D i g i t a l   M a n i f o l d

A

J

H

C

G

E

D

B

F

LOW

HIGH

NITROGEN

NITROGEN

REFRIGERANT

REFRIGERANT

VACUUM

Figure 2

Figure 3

Figure 1

MENU

PAIR

O

Enter

Right

––––

Hold

Left

––––

Max Min

Down

––––

Up

––––

+

  D i g i t a l   M a n i f o l d

A

C

T

E

D

B

LOW

HIGH

CLOSED

T

T

T

Multi-function ¼” 

Male Flare “T” Fitting 

built into the blue hose 

for Simplified 

Purging and Charging 

Refrigerant. 

EZ Access “T” Fitting™

OPEN

Discharge and Purge Hoses

Discharge and Purge Hoses

Pressure Test System

Evacuating System

Charging System

See Figure 1

See Figure 2

See Figure 3

See Figure 3

See Figure 3

A

A

C

E

B

B

D

D

D

A

B

D

D

A

A

A

A

A

C

J

T

C

C

G

G

G

G

E

H

E

E

F

F

F

F

G

F

B

B

D

D

D

D

D

D

A

C

T

E

B

D

D

D

D

Reviews: