background image

272360-UUM-A-0407

Unitary Products Group

7

Continuous Blower:

The blower will run continuously whenever the wall thermostat fan
switch is in the "ON" position. The furnace blower will run at the speed
selected on the "FAN SPEED" jumpers on the main control board (HI
COOL, LO COOL, HI HEAT or LO HEAT).

HOT SURFACE IGNITION SYSTEM

TROUBLESHOOTING

The following visual checks should be made before troubleshooting:

1.

Check to see that the power to the furnace and the ignition control
module is ON.

2.

The manual shut-off valves in the gas line to the furnace must be
open.

3.

Make sure all wiring connections are secure.

4.

Review the sequence of operation. Start the system by setting the
thermostat above the room temperature. Observe the system’s
response. Then use the troubleshooting section in this manual to
check the system’s operation.

FURNACE CONTROL DIAGNOSTICS

The furnace has built-in, self-diagnostic capability. If a system problem
occurs, a blinking LED shows a fault code. The LED can flash red,
green or amber to indicate various conditions. It is located behind a
clear view port in the blower compartment door.

The control continuously monitors its own operation and the operation
of the system. If a failure occurs, the LED will indicate the failure code. If
the failure is internal to the control, the light will stay on continuously. In
this case, the entire control should be replaced, as the control is not
field repairable.

Flash sequence codes 1 through 10 are as follows: LED will turn “on”
for 1/4 second and “off” for 1/4 second. This pattern will be repeated the
number of times equal to the code. For example, six “on” flashes equals
a number 6 fault code. All flash code sequences are broken by a 2 sec-
ond “off” period.

SLOW GREEN FLASH: 

Normal operation.

SLOW AMBER FLASH:

 Normal operation with call for heat.

RAPID RED FLASH:

 Twinning error, incorrect 24V phasing. Check

twinning wiring.

RAPID AMBER FLASH:

 Flame sense current is below 1.5 microamps.

Check and clean flame sensor. Check for proper gas flow.

4

 

AMBER FLASHES: 

The control board is recieving a “Y” signal from

the thermostat without a “G” signal, indicating improper thermostat wir-
ing.

1 RED FLASH:

 This indicates that flame was sensed when there was

not a call for heat. With this fault code the control will turn on both the
inducer motor and supply air blower. A gas valve that leaks through or
is slow closing would typically cause this fault.

2 RED FLASHES:

 This indicates that the normally open pressure

switch contacts are stuck in the closed position. The control confirms
these contacts are open at the beginning of each heat cycle. This would
indicate a faulty pressure switch or miswiring.

3 RED FLASHES:

 This indicates the normally open pressure switch

contact did not close after the inducer was energized. This could be
caused by a number of problems: faulty inducer, blocked vent pipe, bro-
ken pressure switch hose or faulty pressure switch.

4 RED FLASHES:

 This indicates that a primary or auxiliary limit switch

has opened its normally closed contacts. With this fault code the control
will operate the supply air blower and inducer. This condition may be
caused by: dirty filter, improperly sized duct system, incorrect blower
speed setting, incorrect firing rate or faulty blower motor.

 FIGURE 7: 

Furnace Control Board

HI COOL

LO HEAT

EAC-H

L1

XFMR

NEUTRALS

HUM

60

90

120

180

BLOWER DELAY

Y/Y2

W2

R

G

C

Y1

LO COOL

REMOTE

SWITCH

FA

N

SPEED

LO
COOL

LO
HEA

T

HI

COOL

W/W1

HI

HEA

T

W2
DELA

Y

OFF

10
MIN

15
MIN

20
MIN

HI HEAT

YELLOW - MED LOW

BLACK - HI

RED - LOW

BLUE - MED HI

CONTINUOUS
FAN SPEED
JUMPER

W1 - W2
DELAY
JUMPER

FAN OFF
ADJUSTMENT
JUMPER

HOT SURFACE IGNITION SYSTEM
Do not attempt to light this furnace by hand (with a
match or any other means). There may be a potential
shock hazard from the components of the hot surface
ignition system. The furnace can only be lit automatically
by its hot surface ignition system.

Never bypass pressure switch to allow furnace opera-
tion. To do so will allow furnace to operate under poten-
tially hazardous conditions.
Do not try to repair controls. Replace defective controls
with UPG Source 1 Parts.
Never adjust pressure switch to allow furnace operation.

Summary of Contents for FC9T-DH

Page 1: ...sary FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone including cell phone in your building Le...

Page 2: ...e furnace casing making sure the physical support is sound without sagging cracks or gaps Examine the furnace base making sure it is physically sound without cracks gaps or sagging and has a good seal 5 Examine the furnace casing for obvious signs of deterioration 6 Examine the burner flames to make sure they are in good adjust ment Refer to the pictorial sketch shown in Figure 2 as a compari son ...

Page 3: ...ructions 1 STOP Read the safety information above 2 Set the thermostat to the lowest setting 3 Turn off all electric power to the appliance 4 Remove burner door 5 Move gas control switch to the OFF position Do not force 6 Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety information above If you don t smell gas go to next step 7 Move gas control switch to t...

Page 4: ...hed to the cas ing of the furnace or placed in the return air duct You can gain access to the filter by pulling on the door or unscrewing the retaining screw then slide the filter s out of its channel Replace throw away filter s with the same size new filter s Throw away filter s may be replaced with cleanable filter s at this time Cleanable filter s may be cleaned as described in the manufacturer...

Page 5: ...int 3 Remove the burner door and remove the burner box cover 4 Disconnect wires from flame sensor rollout switch and HSI igniter Remove igniter carefully as it is easily broken 5 Remove the screws that hold the burner box assembly to the vest panel and remove the assembly 6 Remove the vent pipe assembly vent blower and condensate pan 7 The heat exchanger is now exposed 8 With a long flexible wire ...

Page 6: ...e Satisfied The Thermostat opens the circuit between R and W1 Immediately the Gas Valve is de energized and Flame Rectifica tion is lost The Inducer Motor is de energized after a 15 second Post Purge and the Hum terminal is de energized The Fan Off Delay circuit is initiated The Delay time can be field set at 60 90 120 or 180 seconds It comes from the fac tory set at 60 seconds The Heat Low termin...

Page 7: ...r Check for proper gas flow 4 AMBER FLASHES The control board is recieving a Y signal from the thermostat without a G signal indicating improper thermostat wir ing 1 RED FLASH This indicates that flame was sensed when there was not a call for heat With this fault code the control will turn on both the inducer motor and supply air blower A gas valve that leaks through or is slow closing would typic...

Page 8: ...cludes a watchdog type circuit that will reset from a lockout condition after 60 minutes Operational faults 6 7 8 will be reset This provides protection to an unoccupied structure if a temporary condition exists causing a furnace malfunction An example would be a low incoming gas supply pressure preventing unit operation When the gas pressure is restored at some point the watchdog would restart th...

Page 9: ...NDUCER LOW STAGE PRESSURE SWITCH HSI 1ST STAGE MAIN VALVE FLAME SENSE LOW CIRCULATOR HEAT SPEED 1ST STAGE LOW PRESSURE SWITCH CLOSE RECOGNITION HSI WARM UP 17 SEC IGNITION ACTIVATION PERIOD 4 SEC TRIAL FOR IGNITION 7 SEC INTER PURGE 60 SEC HSI WARM UP 27 SEC IGNITION DEACTIVATION PERIOD 3 SEC HEAT FAN DELAY ON 30 SEC BURN TIME POST PURGE 15 SEC HEAT FAN DELAY OFF SELECTABLE 60 90 120 180 SEC OFF O...

Page 10: ...Products Group SECTION III REPLACEMENT PARTS LIST 9 5 7 12 54 52 74 75 27 26 25 21 23 24 68 57 67 69 70 61 59 1 15 50 51 18 17 20 45 68 47 49 29 13 5 8 35 52 4 2 41 42 43 46 44 16 14 3 10 13 34 9 6 19 22 28 29 32 31 48 53 58 62 49 ...

Page 11: ...CTOR COMBUSTION BLWR 42 GASKET COMBUSTION BLOWER 43 GASKET CONDENSATE PAN 44 GASKET CONDENSING COIL 45 GASKET GAS CONTROLS 46 GASKET UPPER COND PAN 2 Req d 47 GASKET COMBUSTION AIR TRANSITION 48 GROMMET MANIFOLD SEAL 49 PLUG WINDOW CLEAR 1 5 50 GROMMET MOTOR MOUNT 3 Req d 51 FERRULE MOTOR MOUNT 3 Req d 52 PAN CONDENSATE 53 ORIFICE BURNER Natural 45 54 TRAP CONDENSATE 55 WIRING DIAGRAM 56 HARNESS M...

Page 12: ...ENT TERMINATION KIT 2 ALL MODELS 1CB0317 COMBUSTIBLE FLOOR BASE 17 1 2 CABINET 1CB0321 21 CABINET 1CB0324 24 1 2 CABINET 1TK0917 COIL TRANSITION KIT 17 1 2 CABINET 1TK0921 21 CABINET 1TK0924 24 1 2 CABINET REPLACEMENT PART CONTACT INFORMATION This is a generic parts list To request a complete parts list refer to the contact information below Visit our website at www source1parts com for the follow...

Page 13: ...272360 UUM A 0407 Unitary Products Group 13 SECTION IV WIRING DIAGRAM FIGURE 9 Wiring Diagram ...

Page 14: ...272360 UUM A 0407 14 Unitary Products Group NOTES ...

Page 15: ...272360 UUM A 0407 Unitary Products Group 15 NOTES ...

Page 16: ...nly to products installed in the United States and Canada EXCLUSIONS This warranty does not cover any 1 Shipping labor or material charges 2 Damages resulting from transportation installation or servicing 3 Damages resulting from accident abuse fire flood alteration or acts of God tampering altering defacing or removing the product serial number will serve to void this warranty 4 Damages resulting...

Reviews: