13 Technical data
13.1 Technical data
General
IP
IP20 (IP: degree of inaccessibility to active parts of the product
and degree of water)
Max. ambient RH (relative humidity)
85% at 20 °C
Max. radio distance between controller and thermostat
30 m
Thermostat and timer
CE marking
Low voltage tests
EN 60730-1* and EN 60730-2-9***
EMC (electromagnetic compatibility requirements) tests
EN 60730-1 and EN 301-489-3
ERM (electromagnetic compatibility and radio spectrum matters) tests
EN 300 220-3
Power supply
Two 1.5 V AAA alkaline batteries
Voltage
2.2 V to 3.6 V
Operating temperature
0 °C to +45 °C
Storage temperature
-10 °C to +65 °C
Radio frequency
868.3 MHz
Transmitter duty cycle
<1%
Connection terminals (thermostats only)
0.5 mm² to 2.5 mm²
Controller
CE marking
Low voltage tests
EN 60730-1* and EN 60730-2-1***
EMC (electromagnetic compatibility requirements) tests
EN 60730-1 and EN 301-489-3
ERM (electromagnetic compatibility and radio spectrum matters) tests
EN 300 220-3
Power supply
230 V AC +10/-15%, 50 Hz or 60 Hz
Operating temperature
0 °C to +50 °C
Storage temperature
-20 °C to +70 °C
Maximum consumption
2 W
Relay outputs
230 V AC +10/-15%, 250 V AC 8 A maximum
Power connection
1 m cable with europlug (except UK)
Connection terminals
Up to 4.0 mm² solid, or 2.5 mm² flexible with ferrules
*)
EN 60730-1 Automatic electrical controls for household and similar use
-- Part 1: General requirements
**)
EN 60730-2-1 Automatic electrical controls for household and similar use
-- Part 2-1: Particular requirements for electrical controls for electrical
household appliances
***) EN 60730-2-9 Automatic electrical controls for household and similar use
-- Part 2-9: Particular requirements for temperature sensing controls
13.2 Technical specifications
Cables
Standard cable length
Maximum cable length
Wire gauge
External sensor cable to thermostat
5 m
5 m
0.6 mm²
Floor sensor cable to thermostat
5 m
5 m
0.75 mm²
0682
Usable in all Europe
Declaration of conformity:
We hereby declare under our own responsibility that products dealt
with by these instructions satisfy all essential demands linked to the
R&TTE 1999/5/CE Directive dated March 1999.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
3 6