MIXING ROOM (MIX ROOM)
(See fig. l)
1) Go to MIX ROOM item field in Adjust Menu
2) Set to the desired room temperature for mixing zones
NOTE: There is only a ±3°F (±1°C)
adjustment in the LTD Access Level.
DIP SETTING: Mixing Reset
RANGE: 35 to 100°F (2 to 38°C)
DEFAULT: 70°F (21°C)
NOTE:
Used to shift the reset ratio parallel for
temporarily higher/lower room temperature.
10K INDOOR SENSOR (MIX 10K )
(See fig. m)
1) Go to MIX 10K item field in Adjust Menu
2) To add an indoor sensor for temperature control of a single
zone mixing system, set to INDR
3) To add indoor temperature feedback control from a tekmar
zone control, set to ZoIn
4) To add a slab sensor for temperature control for snow
melting, set to SLAB
RANGE: NONE, INDR, ZoIn, SLAB (only if MIX MIN = OFF)
DEFAULT: NONE
45
PROGRAMMING
PROGRAMMING - Step 1 - Programming the Control
Adjust
o
F
l
Access Level
LTD
USER
INST
ADV
Adjust
m
Adjust
Adjust
Access Level
LTD
USER
INST
ADV
Adjust
Summary of Contents for SYSTEMpro 311
Page 1: ...SYSTEMpro 311 Installation Manual...
Page 90: ...88 APPENDIX II APPENDIX II SYSTEMpro 311 Menu Tree...
Page 91: ...89 APPENDIX II APPENDIX II SYSTEMpro 311 Menu Tree...
Page 92: ...90 APPENDIX III APPENDIX III Application Drawings...
Page 93: ...91 APPENDIX III APPENDIX III Application Drawings...
Page 94: ...92 APPENDIX III APPENDIX III Application Drawings...
Page 95: ...93 APPENDIX III APPENDIX III Application Drawings...
Page 96: ...94 APPENDIX III APPENDIX III Application Drawings...
Page 97: ...95 APPENDIX III APPENDIX III Application Drawings...
Page 98: ...96 APPENDIX III APPENDIX III Application Drawings...
Page 99: ...97 APPENDIX III APPENDIX III Application Drawings...
Page 106: ......