IMPORTANT SAFETY INSTRUCTION

1.

 

WARNING: SAVE THESE INSTRUCTIONS!!

 

 

WARNING: Manual contains important instructions of UPS and batteries during installation 

and maintenance. Follow this instruction at all time. 

 

WARNING:

 It is recommended to install UPS in an ANSI/NFPA75 room in which temperature 

and humidity are controlled and free from electrically conductive particles. 

DO NOT 

expose 

UPS to direct sunlight or high heat source; 

DO NOT

 block off ventilation opening around the 

housing.

 

 

CAUTION:

  Before  conducting  maintenance,  repair,  or  shipment,  please  turn  off  everything 

completely and disconnect them. 

 

CAUTION: 

The  UPS  is 

NOT

  applicable  for  any  inductive  loads  such  as  motors  or  domestic 

appliances like hairdryers, speakers, and fluorescent lamps.

 

 

CAUTION:

  All  interconnection  and  power  cable  should  be  connected 

ONLY  AFTER 

the  UPS 

shut down and disconnected from main. 

 

CAUTION:

 Only use No.26 AWG or larger certified cables to connect UPS and device.

 

 

CAUTION:

 

DO NOT

 unplug UPS from main power during operation or protective ground will 

fail. 

DO NOT

 disconnect battery under load or shut down may occur.

 

 

CAUTION: 

Ensure  the  total  leakage  current  of  UPS  and  the  connected  equipment  under 

3.5mA. 

 

CAUTION: 

Ensure  UPS  connects  to  grounded  main  power  with  a  fuse  or  circuit  breaker 

protection.

 

 

CAUTION:

 Dangerous amount of voltage might still exist even the UPS disconnects from the 

main power since residual voltage exists due to battery supply.

 

 

CAUTION:

 Beware of all the details on the cautionary sticker located on UPS.

 

 

CAUTION  (No  user-serviceable  parts):

  Do  not  attempt  to  remove  the  unit’s  cover,  no 

user-serviceable parts inside. Please refer all service to qualified service technicians.

 

 

CAUTION:

 

DO NOT

 dispose UPS and its batteries to fire, the battery may explode.

 

 

CAUTION:

 

DO NOT

 attempt to open or mutilate the battery.

 

 

User’s operations

: Users only permits to:

 

• Turning the UPS unit on and off. 

• Operating the user interface. 

• Connecting data interface cables. 

 

CAUTION:

 Battery can cause shock and short circuit current. When servicing batteries:

 

A.

 

Remove watches, rings, or other metal objects.

 

B.

 

Use tools with insulated handles.

 

C.

 

Wear rubber gloves and boots.

 

D.

 

Please 

DO NOT

 place any tools or metal parts on top of batteries.

 

E.

 

Disconnect charging source before connecting/disconnecting battery terminals.

 

F.

 

Servicing  of  batteries  should  be  performed  or  supervised  by  personnel  with  necessary 

precautions and knowledge. Keep unauthorized personnel away from batteries.

 

 

DANGER:

  Hazardous  electric  component  inside  this  unit  (example:  Heat-sinks)  remain 

energized from the battery supply even when the main power is disconnected.

 

 

DANGER:

  Battery  circuit  is  not  isolated  from  the  AC  input.  Hazardous  voltage  may  exist  at 

battery terminals and ground—test for safety before any direct contact.

 

 

CAUTION: 

Remove the battery’s pole during service inside the battery cabinet or UPS.

 

 

CAUTION:

 

ONLY

 replace batteries with the same type and quantity.

 

WARNING (Fuses)

: Ensure fuse replacement with the same type and rating 

ONLY

 

Summary of Contents for 1000A/AP

Page 1: ...U P S Line Interactive 425VA 1000VA USER MANUAL ...

Page 2: ...ations If by turning on and off you conclude that the equipment s harmful interference influences your radio or television reception use one of the following preventive measures Place the receiving antenna in a separate location or orientation Ensure a greater distance between the receiver and the equipment Ensure that your Equipment connects to an outlet on a separate circuit Contact a technician...

Page 3: ... panel view 4 3 2 Connection to Main and Load 4 4 Operation 5 4 1 General Description 5 4 2 System Configuration 5 4 3 Panel overview 5 4 4 UPS Control 6 4 5 UPS Configuration 7 5 UPS Monitoring Connection 7 6 Maintenance 8 6 1 Transportation 8 6 2 Storage 8 6 3 Operation 8 6 4 Battery 8 6 4 1 Maintenance 8 6 4 2 Replacement 8 APP A Troubleshooting 9 APP B Technical Specifications 10 ...

Page 4: ...ects from the main power since residual voltage exists due to battery supply CAUTION Beware of all the details on the cautionary sticker located on UPS CAUTION No user serviceable parts Do not attempt to remove the unit s cover no user serviceable parts inside Please refer all service to qualified service technicians CAUTION DO NOT dispose UPS and its batteries to fire the battery may explode CAUT...

Page 5: ...zardous situations to personnel and equipment Ensure the main power voltage matches with UPS 110V 220V For electrical installation closely observe the nominal current rating of the source Check the equipment s power requirement to prevent overloading situations Do not connect devices that draw either massive power shortly or half wave rectified current such as hairdryer vacuum cleaner laser printe...

Page 6: ...y while connected to power During a power failure the UPS will switch to Battery Mode in which power is maintained from the battery In case of failure time exceed Battery Mode duration UPS will shut down until voltage return to prevent battery discharge Diagnostic Test While the advanced battery management system monitors the conditions of the batteries it sends early warnings if a battery replace...

Page 7: ...icates the UPS is over loaded OVER LOAD indicator Red The indicator illuminates when the connected loads exceed the maximum rated capacity Battery level bar It indicates the battery capacity and battery status When the battery capacity is low it becomes dim when the battery needs to be replaced or the charger of UPS is fail to function indicators on all the bar flash Output Voltage This digital in...

Page 8: ...can also be enabled or disabled via monitoring software Green Mode Enable Turn on UPS normally Green mode activates in default Green Mode Disable When turning on UPS please keep holding the ON button until a double beep occurred 4 5 UPS Configuration UPS Manual test Manual tests for UPS or battery can be conducted from the UPS configuration as well and are functional even when the UPS is not charg...

Page 9: ...g to safety instruction otherwise the safety of installation personnel cannot be guaranteed since the unit may malfunction Please ensure no flammable substances such as gases or fumes Avoid extreme temperature and humidity Protect the equipment from moisture Ensure there is enough space 300mm or above recommended at the rear and side of UPS for proper ventilation Ensure that the front of the UPS r...

Page 10: ...low battery power Check the main power connection If operating with battery power ensure enough charging time for UPS Time of pressing the button is too short Press and hold the ON button for a longer duration Output short circuit or overload on UPS Turn off UPS and take off all load Check for any potential internal short circuit Then attempt to turn on UPS again Hardware failure Contact for techn...

Page 11: ... Protection Overload Surge Short Circuit Tele Communication RJ11 RJ45 AP model Battery Type 12V 7 2Ah 12V 9 Ah Quantity 1 1 Typical Recharge Time 6 8 hr to 90 Management Communication Indicator LED Control Panel IMP model Digital Control Panel IMD model Communication Port USB B type AP model Physical Dimensions WxDxH mm 105 x 334 x 168 Weight kgs 6 1 6 1 6 3 6 8 6 8 Shipping Dimensions mm 196 x 41...

Reviews: