3Phase HF UPS 10-120kva USER Manual 

Page27 

7.1.1

 

LCD and menu key 

LCD displays friendly interface and provides lattice graphical display of 260 x 128. It can 

display the alarm information at real-time.   

The  user  can  perform  the  operational  order  through  LCD  display  interface  to 

conveniently  browse  the  input,  output,  load  and  battery  parameters,  so  that  they  can 

acquire  the  real  time  UPS  status  and  alarm  information  and  events.  Besides,  LCD  can 

display the version information of the software of converter, inverter and internal monitor 

board. There are mainly 5 buttons. F1, F2, F3, F4 and ESC on the front panel and under 

different menu the function are different .You can touch the screen or press the button as 

you like; 

ESC means EXIT function 

Tree-structure diagram of menu displayed in LCD is as follows: 

Figure 11: Events list displayed in panel 

user

UPS 

ID set

Output 

set

parallel

Passwo

rd

Main 

MENU

time

Charge

r set

Mainta

in 

telepho

ne

56

64

Advanced

model

Bypass 

set

Input 

set

Battery 

set

Use 

time 
limit

meters

input

Output

(m1)

Battery

(m2)

load

Curren

t  

record

Fault 

recode

Warnin

recode

All

recode

Set 

recode

events

parallel

charger

bypass

setup

information

version

model

service

other

power

Temp.

 

Summary of Contents for ES33 Series

Page 1: ...3Phase HF UPS 10 120kva USER Manual Page1 User Manual ES33 Series Online HF UPS10 120kva 380 400 415Vac ...

Page 2: ...roduction 13 3 2 Safety 13 3 3 Battery cabinet 14 3 3 1 Introduction 14 3 3 2 Environmental temperature 14 3 3 3 Temperature pickup of battery 15 3 3 4 Cable incoming 15 3 3 5 Structural map of battery configuration 15 Note Please pay high attention to the battery connection regarding the Negative Pole the Positive Pole and the Neutral N 15 1 Standard model with internal battery 15 Please refer th...

Page 3: ...nput voltage and frequency of the utility As shown in diagram 1 the utility is inputted from CB1 the rectifier converts the utility to DC The PFC converts the low DC to high DC DC busbar and supplies power to the DC DC battery charger charge the battery at any time and the inverter The inverter converts the DC power to AC power to supply the load When the utility is interrupted the battery supplie...

Page 4: ... Performance parameters Capacity 10 15 20 30 40 50 60 80 100 120kVA Main input Input voltage 380V 400 415V line voltage Input mode Three phase five wire Power factor 0 99 Total Harmonic Distortion Harmonic current 3 Voltage range line voltage 20 25 Frequency range 40 70HZ Bypass input Input voltage 380V 400 415V line voltage Input voltage range 15 25 settable ...

Page 5: ...g range 50 60Hz 3Hz Frequency precision battery inversion 0 01 Three phase separation 120 0 5 Frequency tracking rate Adjustable between 0 5Hz s and 5Hz s Inverter overload capacity 105 load 125 load convert to bypass output after 10min 125 load convert to bypass output after 10S 150 load convert to bypass output after 200ms Load between 105 150 close the inverter according to the overload curve B...

Page 6: ...ion strength Input and output ground 2820Vdc leakage current is lower than 3 5mA 1min without flashover Surge protection Meet the Ⅳ installation location requirement of IEC60664 1 that is the ability of bearing 1 2 50us 8 20us combination wave is not lower than 6KV 3KA Protection degree IP20 Battery number 32 36 38 40 cells of 12V battery Installation Connection mode bottom incoming and outgoing ...

Page 7: ...rent power distribution network and support the transformer optional parts of transferring three wire to four wire If it used for the IT alternating current power distribution network a four grade circuit breaker should be equipped to the input referring to the relevant IT system standard Be careful to the installation of the battery When connect the battery the voltage of the battery terminal wil...

Page 8: ...mediately 7 Check up the product label and confirm the correctness of the equipment The equipment label is fixed behind the door of the equipment And information such as UPS model capacity and main parameters is written in the label 2 3 Storage Keep UPS indoor with well air ventilation to avoid the over wetting or over temperature environment 2 4 Link Connection After the complete position of the ...

Page 9: ... 80 160 125 230 100 200 156 280 120 240 183 345 2 4 3 Public input connection For the bypass and rectification sharing the same circuit of the commercial power input same AC source connect the alternating current input cable to the UPS input terminal main path R S T input N Make sure of the correctness of the phase sequence 2 4 4 Separate bypass connection For the bypass and rectification from two...

Page 10: ...2 5 1 Features of the monitoring panel According to the specific requirement of the site auxiliary connection is required for UPS realizing the function of management of the battery system including the external battery switch and temperature pickup of the battery communication of personal computer warning signal to the external device or remote emergency power off These functions are realized thr...

Page 11: ...tion distance is 25 50m 2 5 2 AS400 Except for the communication protocol as mentioned above this series UPS has AS400 card an optional accessory for AS400 communication protocol Please contact your local distributor for details The following is the pin assignment and description of DB 9 connector in AS400 card Pin Description I O 1 UPS Fail Output 2 Summary Alarm Output 3 GND Input 4 Remote Shutd...

Page 12: ... the background monitoring software RS232 supplies the serial data to use as debugging and maintenance interface of the authorized debugging and maintenance personnel and the switching of the SNMP card 2 5 5 SNMP card interface PW UPS supplies the communication interface of the SNMP card to install the communication option SNMP card optional on site 2 5 6 RS485 is this series inside RS485 communic...

Page 13: ...manually The switch off control can be realized through the under voltage coil of battery switch or release 3 2 Safety The operation of the battery of PW UPS system shall be particularly careful because the voltage of the battery is deadly dangerous when connect all the single batteries With regards to safety the external battery shall be installed in the cabinet with lock or special designed batt...

Page 14: ...n the skin if it contacts the electrolyte 10 Scrap disposal of the battery shall comply with the local environment laws 11 The quantity of new battery and old one shall be the same when replace the battery 3 3 Battery cabinet 3 3 1 Introduction This battery cupboard can be used together with other machine cabinets so that it can contain more batteries to provide the system longer backup support ti...

Page 15: ...y at the top and it is connected directly to UPS control system If use the control panel of the battery switch connect UPS control system through the control panel of battery switch This function can regulate the float charge voltage of battery to make it inversely proportional to battery cupboard room temperature So the battery can be protected from over charge under high temperature enviroment 3...

Page 16: ...with external battery Battery quantity from 14 20PCS settable on LCD screen Please refer the Diagram 17 2 Battery connection as below Diagram 17 2 Battery connection 3 4 Power cable of battery 3 4 1 Installation of battery 1 Generally the space between the vertical surface and the sides shall be at 1 10 mm ...

Page 17: ...or these cables can pass through the machine cabinet through the underside incoming hole of battery cupboard 2 Generally it suggests connecting the cables between the same layer batteries first and then connecting the cables between the layers finally connecting the battery switch and battery terminals 3 Install the insulating cover to the terminals after connecting the battery terminals 4 Connect...

Page 18: ...ical 1 N system principle Note The internal maintaining bypass switch CB3 must be taken off when the load exceeds the capacity of single machine All the single machines must be connected with double insulated shielding parallel controlled cable of 30m longest ...

Page 19: ...ation software Normally the host and slave are operated of inverted supply mode and the output of the slave UPS single machine connects to the bypass input of the host UPS The output of the host UPS is to be connected with the load and synchronize with slave UPS When the inverter of host UPS connected with the load happened with fault power supply will be provided by the slave UPS for the load thr...

Page 20: ... similar to single system machine the different is to connect the output of superior host UPS with the bypass input of the subordinate slave UPS in the hot backup system and the subordinate UPS supplies the load through its inverter or bypass Besides the input power supply of the bypass and main path must use the same neutral wire input terminal ...

Page 21: ...3Phase HF UPS 10 120kva USER Manual Page21 Section V Installation Diagram 5 1 External structure Diagram 21 External view of overall machine 5 2 Internal view ...

Page 22: ...al structure 1 Terminalblock BATTERY N N U V W OUTPUT N R S T BYPASS N R S T INTPUT PE G NOTES 1 when doing cable connection for standard model with inbuilt battery please pay high attention to pull off all the battery terminals red cable showed in below diagram ...

Page 23: ...Connect the AC battery and load well and pay attention to the cable diameter and R S T phase sequence 2 Switch on AC input bypass and output breaker and if it s long time model switch on battery breaker 3 At this time fan is running and UPS will self test one time and after 5s UPS into bypass mode as below ...

Page 24: ...0 120kva USER Manual Page24 4 Press ON button for above 3s UPS will run into start up process and after about 10s UPS will be in LINE mode as below 5 6 Switch off AC breaker UPS will transfer to battery mode as below ...

Page 25: ... VII Operational Controlling Display Panel 7 1Introduction The operational display panel of UPS is mounted on the front panel Through which UPS can be operated and controlled to inquire the parameters UPS battery states and events alarm information etc This panel can be divided into three parts by its functions including simulation state diagram LCD display menu key and control operational key Sim...

Page 26: ...f display panel LED Function Button Function parallel UPS work for parallel mode EPO Emergency power off EPO switch normal UPS is normal ON Start up switch of inverter warning Attention please OFF Turn off switch of inverter fault UPS in fault mode Alarm silence switch Input bypass bat inv output simulation state diagram ESC RETURN exit F1 F2 F3 F4 LCD menu key Remark Function varying under differ...

Page 27: ...ter inverter and internal monitor board There are mainly 5 buttons F1 F2 F3 F4 and ESC on the front panel and under different menu the function are different You can touch the screen or press the button as you like ESC means EXIT function Tree structure diagram of menu displayed in LCD is as follows Figure 11 Events list displayed in panel user UPS ID set Output set parallel Passwo rd Main MENU ti...

Page 28: ...ndards Figure 15 European and international standard Item Standard General safety requirements of UPS operational area EN 50091 1 1 IEC 62040 1 1 AS 62040 1 1 EMC Requirements of UPS EN 50091 2 IEC 62040 2 AS 62040 2 Class A UPS property confirmation method and test requirements EN 50091 3 IEC 62040 3 AS 62040 3 VFI SS 111 The environmental features of the product are as follows Figure 16 Environm...

Page 29: ... temperature 20 70 The mechanical features of the product are as follows Figure 17 Mechanical features of UPS Physical Capacity 10KVA 9KW 15KVA 13 5KW 20KVA 18KW 30KVA 27KW 40KVA 36KW Unit Dimension Long run 390 850 977MM W D H 500 717 1150 MM W D H Unit Dimension Inbuilt batt 390 850 977MM W D H 500 717 1550 MM W D H Weight KG Long run 110 130 130 150 152 172 160 190 160 190 Weight KG Inbuilt Bat...

Page 30: ...0 Physical Capacity 60KVA 54KW 80KVA 72KW 100KVA 90KW 120KVA 108KW Unit Dimension UPS 600 850 1680 MM W D H 735 850 1680 MM W D H Unit Dimension Packing 954 704 1857 MM W D H 954 839 1857 MM W D H Weight N G KG 240 280 260 300 320 360 340 380 ...

Reviews: