3Phase HF UPS 10-120kva USER Manual
Page29
1 meter
Sea
level
height
m
≤
3000m
The power reduces 1% when it increases 100m within 3000~8000m
Relative
humidity
—
0~95%, no condensation
Operating
temperature
℃
0~40 note: The service life of the battery will be shorten half when it
increases 10
℃
above 20
℃
UPS
storing-transp
ortation
temperature
℃
-20~70
The mechanical features of the product are as follows:
Figure 17: Mechanical features of UPS
Physical
Capacity
10KVA/9KW
15KVA/13.5KW
20KVA/18KW
30KVA/27KW
40KVA/36KW
Unit Dimension
(Long-run)
390*850*977MM
(W*D*H)
500×717×1150 MM
(W*D*H)
Unit Dimension
(Inbuilt batt.)
390*850*977MM
(W*D*H)
500×717×1550 MM
(W*D*H)
Weight (KG)
(Long -run)
110/130
130/150
152/172
160/190
160/190
Weight (KG)
(Inbuilt Batt.)
182/202
202/222
216/236
331/361
367/397
10kva and 15kva:inbuilt 36pcs 7ah
20kva: inbuilt 36pcs 9ah
(72pcs 7ah)
(72pcs 9ah)