8 Specifications
8. 1 Electrical
Model
1K
1KS/1KL
2K
2KS/2KL
3K
3KS/3KL
Rating
1KVA/800W
2KVA/1600W
3KVA/2400W
Input
Input system
Single phase & earth ground
Voltage range
(90±5)VAC~ (290±5)VAC
Power factor
≥0.99
Voltage range of
bypass
(80±5)VAC~ (286±5)VAC (default: 80VAC~264VAC
Could be adjusted by software)
Output
Output system
Single phase & earth ground
Rated voltage
220VAC
①
Power factor
0.8
Voltage precision
±2%
Output
frequency
Normal
mode
1.The output frequency synchronizes with the input
frequency when the input frequency is in the range of
46 Hz~ 54 Hz
2.The output frequency is 50Hz when the input frequency
is not in the range of 46 Hz~ 54 Hz
3.Can be set as 60Hz
Battery
mode
Inverter overload
capacity (Utility
power
,
25
℃
)
105%±5%<Load≤125%±5% 50s transfer to bypass
125%±5%< Load <150%±5% 25s transfer to bypass
Load > 150%±5%,300ms transfer to bypass
Transfer time
0ms (Normal mode←→ Battery mode
)
<4ms (Normal mode←→Bypass mode
)
Crest factor
3:1
Battery
Batteries voltage
36VDC
72VDC/96VDC
96VDC/72VDC
Battery Quantity
3
none
6/8
none
8/6
none
Battery Type
Sealed maintenance-free lead –acid battery of battery
voltage 12V/7AH
Backup Time (25
℃
)
Full load≥5min (Standard)
Charge current
1A
6.5A
1A
5.5A
1A
5.5A
①
Note1: Output voltage can be set: 200V/208V/220V/230V/240V.