3. Installation
3) For 10K(L)/31 10KL UPS, it is recommended to select the UL1015
8AWG (10 mm
2
) wire or other insulated wire which complies with
AWG Standard for the UPS input and output wirings.
4) For 31 12KL/31 15KL/31 20KL UPS, it is recommended to select the
UL1015 6AWG (25mm
2
) wire or other insulated wire which complies
with AWG Standard for the UPS input and output wirings.
Note: Do not use the wall receptacle as the input power source for the
UPS, as its rated current is less than the UPS’s maximum input
current. Otherwise the receptacle may be burned and destroyed.
(Please refer to section 1.4)
5) Connect the input and output wires to the corresponding input and output
terminals according to the following diagram.
Note: You must make sure that the input and output wires and the input
and
output terminals are connected tightly.
6) The protective earth ground wire refers to the wire connection between
the equipment which consumes electro-equipment and the ground wire.
The wire diameter of protective earth ground wire should be at least as
above mentioned for each model and green wire or green wire with
yellow ribbon wire is used.
7) After having completed the installation, make sure the wiring is correct.
8) Please install the leak current protective breaker at the output power
distribution panel of the UPS if necessary.
9) To connect the load with the UPS, please turn off all the loads first, then
perform the connection and finally turn on the loads one by one.
10) No matter the UPS is connected to the utility power or not, the output
of the UPS may have electricity. The parts inside the unit may still have
hazardous voltage after turning off the UPS. To make the UPS have no
output, power off the UPS, and then disconnect the utility power
supply.
11) Suggest charging the batteries for 8 hours before use. After connection,
turn the input breaker in the “ON” position, the UPS will charge the
batteries automatically. You can also use the UPS immediately without
charging the batteries first, but the backup time may be less than the
standard value.