PV Module Installation Instructions
5
/
12
◇
Comply with the safety requirements of all other modules used in the system,
including wiring lines and cables, connection devices, charging controllers,
inverters, batteries and rechargeable batteries.
◇
Use the equipment suitable for solar power system, connection device, wiring lines
and support frame only. In a particular photovoltaic system, use a type of module as
much as possible and use the same type of the module in the same PV array only.
Each input voltage of the same tracking system of each inverter must be equal and
the same type of modules must be used.
◇
Under normal outdoor conditions, the current and voltage generated by the module
are different from those listed in the parameter table. The parameter table is
measured under the standard test conditions (1000w/m2 irradiance, AM 1.5
spectrum, 25°c temperature), so when determining other modules’ rated voltage,
conductor capacity, fuse capacity, controller capacity and other parameters
correlated to module output power, it should refer to the value of short-circuit
current and open circuit voltage marked on the module and design and install the
module according to the value of 125%.
◇
The modules should be used in the ambient temperature ( -40
℃
~+85
℃
) area where
the component is applicable.
4.
Unpacking and Storage
◇
When receiving the goods, you should check whether the goods delivered are
indeed ordered goods: the outside of each box are marked with the product name,
packaging box number, module barcode.
◇
The packaging carton should be stored in a clean, dry area, away from direct
sunlight and moisture.