MANOWNROSM
TROUBLESHOOTING
US Filter
29
5.9
SYSTEM SHUTOFF, HIGH TEMPERATURE
A.
Check permeate flow. Without permeate flow, water will heat up.
B.
Check incoming water temperature.
C.
The high temperature shut down is activated at 35
°
C ± 3
°
C (95
°
F ± 5
°
F).
D.
The temperature thermistor is located in the feed conductivity probe. The probe
may be replaced if it is giving an erroneous temperature indication.
5.10
LOW PERMEATE FLOW RATE
A.
Adjust the pump throttle valve to increase membrane feed pressure. Do not
exceed 24.15 bar (350 psig).
B.
Permeate piping should be of sufficient I.D. to prevent back pressure on the
system.
C.
For low temperature effects, check permeate flow rate versus temperature curve
in the Appendix.
D.
If adjusting the pump throttling valve does not improve permeate flow rate, the
RO membranes are fouled and should be cleaned with an appropriate medium.
Depending on the type of fouling suspected, various regeneration/cleaning
solutions may be used. Consult your US Filter representative for advice.
CAUTION
Certain solutions, especially those containing chlorine or bromine, can
permanently damage the membranes.
5.11
MOTOR OVERLOAD SHUTDOWN
A.
Motor overload shutdown is caused by excessive amp draw. An overload relay
is provided with the motor magnetic starter to shut the system down if it runs
above the service factor amp rating of the motor.
(Service Factor amp = full load amps x service factor)
B.
Check flows per the System Specifications sheet in the Appendix, and adjust if
necessary. Running pump beyond the rated flow capacities can cause deviation
in amp draw.
C.
Perform an insulation resistance test following the procedure in the
Pump
Installation and Operating Instructions Manual
in the Appendix of this manual. If
the ohm values are less than 20 megohm replace the motor leads.
D.
Liquid end of pump may be damaged or binding.
5.12
CONTROLLER MALFUNCTION
The control box may be changed out in its entirety, if necessary, or the controller board
may be replaced independently.