52
2. My dual gate will not
operate. (Ranger II)
Verify monitored
entrapment device
switches are set
correctly. See installing
monitored entrapment
devices section.
1. Follow steps 1 through 7 above.
2. Disconnect the actuator connectors plugged into the control board
Gate 1 and Gate 2 (X1 and X2). Then locate the DS1 dipswitches on
the control board. Turn off switch 4 (down on left side) and turn on
switch 3 (down on the right side).
Reconnect the connector from the actuator that goes to the gate
closest to you. Connect it to the Gate 1 (X1) connector on the
control board. Press the “Open/Close Command” button and verify
that the gate operates.
3. If the gate operates correctly, disconnect the actuator plug and
connect the other actuator plug into the Gate 1 (X1) connector.
Press the “Open/Close Command” button and verify that the gate
operates correctly. At this point you have tested each actuator
individually. If both worked correctly in Gate 1 then go back to DS1
and turn switch 3 off and switch 4 on. Then repeat step 2 and 3
again using Gate 2 (X2) connector on control board in place of Gate
1 (X1).
4. If a problem is observed in steps 2 or 3 above most likely it was
when the Gate 2 actuator (located the greatest distance from control
box) was being tested. If this is correct check wiring splices for
moisture, correct wiring etc. If the wiring is not in watertight conduit,
this is most likely the problem. Tape is not watertight. Splices should
never be underground.
3. My single or
Dual gate will not
operate.Monitored
entrapment devices
are installed.
Identify the monitored
entrapment device/
devices installed - Photo
Eye or Contact Edge.
Contact Edge with 10K resistor monitoring -
1. Verify that dip switch DS1 switch 10 (contact edge monitor) is ON
pressed down on the right hand side..
2. Press and hold the LED indicator on the control board.
3. Verify the D5 LED (Contact edge 2nd entrapment) located bottom
left corner of the control board is ON dimly.
4. If not using a DC voltmeter measure the voltage on J2 pin 6 to
ground reading should be approx. 2.5 Vdc.
5. Activate the contact edge by depressing it and verify the D5 LED is
ON bright now or the voltage drops to 0 Vdc.
6. If reading is 5 Vdc then check wire connections from contact edge
for proper connection.
7. If wire connections are correct then disconnect the contact edge
wires from the J2 connector.
8. Using an ohm meter verify the resistance measured between the 2
contact edge wires, should be 10K.
9. If not contact edge is bad.