15
Figure 24
F ac to r y def au l t p o si ti o n s.
Sw i tc h 3 show n i n t h e “ON” po si ti o n.
A l l o t he r s show n i n t h e “ O F F ” p o s i ti o n.
Adjusting Close Limit Utilizing Nudge Technique
Nudge adjustment:
(only applies when adjusting close limit)
1.
Turn on control dip switches 3 and 4
2.
Connect linear actuator cable to Gate 1 on control board
3.
Press the Open/Close Command button
4.
Gate will go to the pre set close position
5.
If gate needs to close more turn the gate 1 close limit dial clockwise until desired
close position is achieved.
*Can also be nudged on the gate 2 connector in the same manner (use gate 2 adjustment)
Dual Gate Nudge:
Adjustment must be done one gate at a time. Adjust first gate as stated
above. Then disconnect the actuator cable and connect second gate to Gate 2 on control
board. Follow same procedure for Gate 2 aligni ng it with Gate 1 in the closed position.
Connect both Gate 1 and Gate 2 at this time to verify correct positions.
NOTE:
If nudge is not used simply turn limit dial and cycle gate to see affect.
Installing Safety Signs
Mount safety signs on inside and outside of the gate area so they are clearly visible. Two signs are provided.
Ranger Control Board Information
The Ranger control board is capable of operating two gates. If your installation is a single gate you can operate
the gate on the Gate 1 or Gate 2 connector. Set control switch “ON” for the connector being used.
The Ranger gate operator was shipped with the receiver and entrapment siren already connected to the control
board; these connections are plugs that can easily be disconnected. External reset cable connects to J4.
J2 Terminal: (Accessory Wiring)
Accessories wire to the J2 connector. Insert wire and tighten screw. J2 pin functions are listed below.
J2 pin 1
+12 VDC output for any accessory power needed (100 ma max).
J2 pin 2
Ground connection for any accessory item.
J2 pin 3 Receiver input (connect N/O from device here) (Logic is move, stop, reverse)
J2 pin 4 Solenoid Lock Power output (+12 VDC only) connect solenoid lock power lead here.
(750 ma)
J2 pin 5 Photo Eye Power output (+12 VDC only) connect photo eye power lead here.
J2 pin 6 Mag lock power +12 vdc lock only (750 ma max)
J2 pin 7 Secondary entrapment device input (N/O connection).
J2 pin 8 Optional relay N/O normally open
J2 pin 9 Open / Free Exit sensor input for opening the gate only (N/O connection)
J2 pin 10 Under gate loop / Shadow loop (Connect N/O from device here)
J2 pin 11 Safety reversing input (Photo eye, loop connect N/O from device here)
J2 pin 12 Optional relay common
J2 pin 13 Optional relay N/C normally closed contact
Figure 23