X.
SYSTEM DESCRIPTION & SPECIFICATIONS
Page - 62
Quantity
1
Manufacturer
SamFlow
Construction
316 Stainless steel
Type
Needle
Sample Valve (Feed / Reject)
Quantity
2
Manufacturer
Asahi
Construction
PVC
Type
Labcock
Sample Valve (Product)
Location
One on each vessel product
One on common product
Manufacturer
US Filter / IonPure
Construction
316 stainless steel
Type
Sanitary weld
High Voltage Panel
Quantity
1
Enclosure rating
NEMA 12
Enclosure Finish
Poly urethane
Service
460v-3
-60hz
Main Panel
Quantity
1
Enclosure rating
NEMA 12
Enclosure Finish
Poly urethane
Service
From high voltage panel
J)
Operating Limits
The following limits are the maximum and minimum limits of the various
parameters for the RO membranes and unit components. The system designs are
based on the variables listed in “Design Parameters” at the beginning of the
reverse osmosis specifications.
Maximum Feed Temperature..................45
C
Maximum Feed Pressure........................100 PSIG
Maximum Feed SDI Rating....................5
Maximum Feed Turbidity.......................1 NTU
Maximum Feed Free Chlorine................0
.
1 PPM
Maximum Feed pH (continuous).............11
Minimum Feed pH (continuous)..............2
Maximum pH (cleaning - 30 min.)..........12
Minimum pH (cleaning - 30 min.)............1
K)
Equipment Specifications