CLEARANCES TO COMBUSTIBLES
INSTALL ALL VENTS AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER!
When your Pellet Stove Room Heater is being installed on a combustible
fl
oor it is mandatory that a 1/2” (13mm) thick non-
combustible hearth pad be installed under the heater. The non-combustible hearth pad must extend at least 6” beyond the
fuel loading and ash removal openings and at least the depth of the heater plus 6 inches (152mm) out in front of the heater.
BACK WALL
Figure 5
Figure 6
Alcove Dimensions
36”
35”
40”
2”
6”
USA 6”
CANADA 8”
FLOOR PROTECTION
USA 6”
CANADA 18”
2”
FLOOR
PROTECTION
USA 6”
CANADA 8”
USA 6”
CANADA 18”