background image

© 2011 UTC Fire & Security. All rights reserved. 

1 / 8 

P/N 55300830-04 • REV 4.0 • ISS 11NOV11 

 

DM2010 Manual Call Point Installation Sheet 

EN  DA  ET  IT  LT  LV  PL  SV 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EN: Installation Sheet 

Description  

This document includes installation information for UTC Fire & 
Security DM2010 manual call points. These manual call points 
are designed for use in UTC Fire & Security Aritech analogue 
addressable fire alarm systems and include models for indoor 
and outdoor use. 

Installation 

Caution: 

This product must be installed by qualified personnel 

adhering to the CEN/TS 54-14 standard and any other 
applicable local authority laws. 

Electrical connections 

Connect to the DM2010 connection block (Figure 

2

) as follows: 

1.  Line in (positive) 
2.  Line out (positive) 
3.  Line in (negative) 
4.  Line out (negative) 

Addressing 

Use the DIP switch (Figure 1) to allocate a device address 
from 1 to 128 (see page 8). 

Maintenance 

Basic maintenance consists of a yearly inspection. Do not 
modify internal wiring or circuitry. 

Specifications 

 
Voltage 

17 to 28 VDC

 

Current consumption 
 Standby 
 Alarm 

 
max. 250 

ų

max. 2.5 mA

 

Cable size 
 Minimum 
 Maximum

 

 
0.8 mm

2

 

2.5 mm

2

 

IP rating 
 DM2010, 

DM2010-18 

 DM2010E, 

DM2010E-18 

 
IP24D 
IP67

 

Operating environment
 Operating 

temperature 

 Storage 

temperature

 Relative 

humidity 

 

10°C to +70°C 

20°C to +70°C 

10% to 95% noncondensing

 

Dimensions (W × H × D) 
 DM2010, 

DM2010-18 

 DM2010E, 

DM2010E-18

 

 
89 x 93 x 27.5 mm [1] 
97.5 x 93 x 27.5 mm [1]

 

Weight

 

187 g

 

[1] Excluding surface mount

 

 

Summary of Contents for Aritech DM2010

Page 1: ...trical connections Connect to the DM2010 connection block Figure 2 as follows 1 Line in positive 2 Line out positive 3 Line in negative 4 Line out negative Addressing Use the DIP switch Figure 1 to allocate a device address from 1 to 128 see page 8 Maintenance Basic maintenance consists of a yearly inspection Do not modify internal wiring or circuitry Specifications Voltage 17 to 28 VDC Current co...

Page 2: ...er til både indendørs og udendørs brug Installation Advarsel Dette produkt skal installeres af uddannede personer i overensstemmelse med CEN TS 54 14 standarden og andre relevante lokale love Elektriske forbindelser Forbind klemrækken på DM2010 Se figur 2 som følger 1 Linje ind positiv 2 Linje ud positiv 3 Linje ind negativ 4 Linje ud negativ Adressering Brug DIP switchen figur 1 til at konfigurer...

Page 3: ...kuni 28 V AV Voolutarve Jõudeolekus Häire maks 250 ųA maks 2 5 mA Kaabli suurus Min Maks 0 8 mm 2 2 5 mm 2 IP nimiandmed DM2010 DM2010 18 DM2010E DM2010E 18 IP24D IP67 Töötemperatuur 10 C kuni 70 C Säilitustemperatuur 20 C kuni 70 C Suhteline õhuniiskus 10 kuni 95 Mõõtmed L K S DM2010 DM2010 18 DM2010E DM2010E 18 89 x 93 x 27 5 mm 1 97 5 x 93 x 27 5 mm 1 Kaal 187 g 1 Välja arvatud pinnapaigaldus R...

Page 4: ... prodotto verificare le prime due cifre del numero di serie del prodotto stesso Riferirsi all etichetta di identificazione prodotto Certificazione CPD Certificato DM2010 DM2010 18 DM2010E DM2010E 18 DM201006 KIT 0832 CPD 0753 0832 CPD 0755 0832 CPD 0754 EN54 EN 54 11 Type A I prodotti contrassegnati con questo simbolo non possono essere smaltiti nei comuni contenitori per lo smaltimento rifiuti ne...

Page 5: ...iau informacijos rasite šioje interneto svetainėje www recyclethis info Informacija pasiteirauti Informacijos kaip susisiekti ieškokite interneto svetainėje www utcfireandsecurity com LV Uzstādīšanas rokasgrāmata Apraksts Šajā dokumentā ir ietverta rokas signāldevēju UTC Fire Security DM2010 uzstādīšanas informācija Šie rokas signāldevēji ir paredzēti izmantošanai UTC Fire Security Aritech analoga...

Page 6: ...trznego Instalacja Uwaga Produkt musi montowac wykwalifikowany technik Podczas montazu nalezy stosowac sie do normy CEN TS 54 14 oraz innych obowiazujacych przepisów lokalnych Przyłączenia s Przyłączyć ROP DM2010 do instalacji zaciskami w kostce połączeniowej rysunek 2 następująco 1 Wejście pętli plus 2 Wyjście pętli plus 3 Wejście pętli minus 4 Wyjście pętli minus Adresowanie Adres urzadzenia od ...

Page 7: ... inspektion Ändra inte internt kablage eller kretsar Tekniska specifikationer Driftspänning 17 till 28 VDC Strömförbrukning Vilström Larm max 250 ųA max 2 5 mA Kabelstorlek Min Max 0 8 mm 2 2 5 mm 2 IP märkning DM2010 DM2010 18 DM2010E DM2010E 18 IP24D IP67 Drifttemperatur 10 C till 70 C Lagringstemperatur 20 C till 70 C Relativ fuktighet 10 till 95 icke kondenserande Dimensioner B H D DM2010 DM20...

Page 8: ...31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 ...

Reviews: