© 2011 UTC Fire & Security. All rights reserved.
1 / 8
P/N 55300830-04 • REV 4.0 • ISS 11NOV11
DM2010 Manual Call Point Installation Sheet
EN DA ET IT LT LV PL SV
1
2
EN: Installation Sheet
Description
This document includes installation information for UTC Fire &
Security DM2010 manual call points. These manual call points
are designed for use in UTC Fire & Security Aritech analogue
addressable fire alarm systems and include models for indoor
and outdoor use.
Installation
Caution:
This product must be installed by qualified personnel
adhering to the CEN/TS 54-14 standard and any other
applicable local authority laws.
Electrical connections
Connect to the DM2010 connection block (Figure
2
) as follows:
1. Line in (positive)
2. Line out (positive)
3. Line in (negative)
4. Line out (negative)
Addressing
Use the DIP switch (Figure 1) to allocate a device address
from 1 to 128 (see page 8).
Maintenance
Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry.
Specifications
Voltage
17 to 28 VDC
Current consumption
Standby
Alarm
max. 250
ų
A
max. 2.5 mA
Cable size
Minimum
Maximum
0.8 mm
2
2.5 mm
2
IP rating
DM2010,
DM2010-18
DM2010E,
DM2010E-18
IP24D
IP67
Operating environment
Operating
temperature
Storage
temperature
Relative
humidity
−
10°C to +70°C
−
20°C to +70°C
10% to 95% noncondensing
Dimensions (W × H × D)
DM2010,
DM2010-18
DM2010E,
DM2010E-18
89 x 93 x 27.5 mm [1]
97.5 x 93 x 27.5 mm [1]
Weight
187 g
[1] Excluding surface mount