7.1
95-8533
2-7
Communication wire segment lengths are
dependant upon physical and electrical
characteristics of the cable. Refer to the
installation section for Lon cable wire
information.
no more than six network extenders may be
used on the communication loop.
When a network extender is installed in the
communication loop, up to 40 field devices can
be installed per network segment. the network
segment is the wiring segment between two
network extenders or between a network
extender and a controller.
EQ21xxps series power supplies and
EQ2100psm power supply monitor
The Power Supply, Power Supply Monitor, and backup
batteries are used to provide power to the system.
The power supply monitor communicates trouble
conditions to the Controller. Monitored status
conditions include: power supply failure, loss of AC
power, loss of battery power, power ground fault, AC
and DC voltage (hi/low level), and backup battery
current charge levels.
EQ211xps, EQ213xps and EQ217xps power
supplies
The Power Supply provides main and backup power
to the EQP System. The device includes many
features such as voltage regulation, high efficiency,
and high power factor.
An equalize switch is located on the front panel of the
charger for manual activation, or a multi-mode
electronic timer can be used for automatic activation.
Steady state output voltage remains within +/– 1/2%
of the setting from no load to full load for AC input
voltages /– 10% of the nominal input voltage.
EQ2220GFm Ground Fault monitor
The EQ2220GFM Ground Fault Monitor (see Figure
2-8)
provides ground fault monitoring in a system that
includes a floating 24 Vdc power source. The device
detects ground fault conditions on +/– power and all
secondary I/O circuits. A positive or negative ground
fault condition is indicated immediately by local
LEDs, and by a relay contact after a 10 second time
delay. The ground fault monitor is intended to be
mounted in the same enclosure as the controller.
FiELD DEViCEs
Flame Detectors
For flame detector installation, operation,
maintenance, specifications and ordering information,
refer to Table 2-5.
For information regarding USCG Approval of the
X3301 Flame Detector, refer to Appendix D.
Table 2-5—Flame Detector Manuals
Detector
manual number
X3301
95-8527
X3301A
95-8527 & 95-8534
X3302
95-8576
X5200
95-8546
X2200
95-8549
X9800
95-8554
UVHT
95-8570
Figure 2-8—Ground Fault Monitor
Figure 2-7—Eagle Quantum Premier Network Extender
Summary of Contents for DET-TRONICS 95-8533
Page 128: ...7 1 95 8533 A 4 Figure A 1 System Drawing 007545 001 ...
Page 129: ...95 8533 A 5 7 1 Figure A 2 System Drawing 007545 001 ...
Page 131: ...95 8533 7 1 B 2 Figure B 1 Drawing 007546 001 ...
Page 132: ...95 8533 7 1 B 3 Figure B 2 Drawing 007546 001 ...
Page 134: ...95 8533 7 1 C 2 Figure C 1 Drawing 007547 001 ...
Page 141: ...95 8533 7 1 D 7 Figure D1 System Drawing 007545 001 ...
Page 143: ...APPENDIX E E 1 95 8533 7 1 ...