7.1
3-4
95-8533
Table 3-2—
Alarm Current Requirements at 24 vdc
Device Type
Number of Devices
Alarm Current
Total Current for Device Type
EQP Controller
X
0.430
=
EDIO 8 Inputs
X
0.130
=
EDIO 8 Outputs
X
0.075
=
DCIO 8 Inputs
X
0.130
=
DCIO 8 Outputs
X
0.075
=
Relay Module
X
0.120
=
Power Supply Monitor
X
0.060
=
IDC/IDCGF/IDCSC
X
0.090
=
X3301/X3301A - w/o heater
X
0.160
=
X3301/X3301A - with heater
X
0.565
=
X3302 - without heater
X
0.160
=
X3302 - with heater
X
0.565
=
X2200
X
0.135
=
X9800 - without heater
X
0.085
=
X9800 - with heater
X
0.420
=
X5200 - without heater
X
0.155
=
X5200 - with heater
X
0.490
=
DCUEX
X
0.160
=
DCU with EC Sensor
X
0.075
=
DCU with PointWatch
X
0.320
=
DCU with DuctWatch
X
0.320
=
Analog Input Module
X
0.300
=
Intelligent Protection Module
X
0.150
=
EQ2220GFM
X
0.018
=
PIRECL
X
0.275
=
OPECL Transmitter
X
0.220
=
OPECL Receiver
X
0.220
=
ARM
X
0.120
=
SAM
X
0.120
=
Network Extender
X
0.090
=
EQ21xxPS Power Supply
X
0.350
=
Other
X
=
Total Solenoid Load
+
Total Signaling Load
+
Total
Alarm Current for System (in amperes)
=
Note: This table is for battery calculations only.
Summary of Contents for DET-TRONICS 95-8533
Page 128: ...7 1 95 8533 A 4 Figure A 1 System Drawing 007545 001 ...
Page 129: ...95 8533 A 5 7 1 Figure A 2 System Drawing 007545 001 ...
Page 131: ...95 8533 7 1 B 2 Figure B 1 Drawing 007546 001 ...
Page 132: ...95 8533 7 1 B 3 Figure B 2 Drawing 007546 001 ...
Page 134: ...95 8533 7 1 C 2 Figure C 1 Drawing 007547 001 ...
Page 141: ...95 8533 7 1 D 7 Figure D1 System Drawing 007545 001 ...
Page 143: ...APPENDIX E E 1 95 8533 7 1 ...