7.1
95-8533
4-24
EDIO Startup
1. The Power-on LED should be illuminated. The
Fault LED should blink once on power up, then
remain off.
2. The input circuits should indicate the proper state
of the input device (channel active LED illuminates
when the circuit is closed). Check the input
power supply and associated wiring. Verify
proper voltage per the Troubleshooting matrix.
3. The output circuits should indicate the proper
state for the programmed device (channel active
LED illuminates when the circuit is active). Check
the power supply and associated wiring. Verify
proper voltage per the Troubleshooting matrix.
4. The circuits should not indicate a fault condition
(channel fault LED illuminates when the circuit is
in fault). Check the end-of-line devices and
associated wiring. Verify proper voltage per the
Troubleshooting matrix.
5. Test the entire system for proper operation to
ensure that the configuration was performed
properly.
STARTUP PROCEDURE for DCIO MODULE
Configuration
The DCIO Module is an eight-channel device. Each
channel is capable of being configured as an input or
output, independent of any other channel.
Note
the module is configured using Det-tronics
Safety System Software.
Activation Time
Timers are made available for output circuits only.
Timers are used primarily to set the timing of output
release in a suppression system. Timers provide a
pulse timed output for the time period specified in the
configuration of the channel. The channel output
goes active when commanded by the system logic
and remains on until the timer expires.
Static Logic Mode
Each input channel can be configured as a Fire
Alarm, Trouble, Low Gas Alarm, High Gas Alarm,
Supervisory, or Other type of channel, independent of
any other channel configuration. The type selected
determines the logic the system uses to configure
Indicators, Alarms and Messages.
For example: When an input is selected as Fire type,
the Fire LED on the Controller and Audible alarm will
automatically actuate when that input channel is
active.
Summary of Contents for DET-TRONICS 95-8533
Page 128: ...7 1 95 8533 A 4 Figure A 1 System Drawing 007545 001 ...
Page 129: ...95 8533 A 5 7 1 Figure A 2 System Drawing 007545 001 ...
Page 131: ...95 8533 7 1 B 2 Figure B 1 Drawing 007546 001 ...
Page 132: ...95 8533 7 1 B 3 Figure B 2 Drawing 007546 001 ...
Page 134: ...95 8533 7 1 C 2 Figure C 1 Drawing 007547 001 ...
Page 141: ...95 8533 7 1 D 7 Figure D1 System Drawing 007545 001 ...
Page 143: ...APPENDIX E E 1 95 8533 7 1 ...