background image

 

4 / 8 

 

P/N 3101999-ML • REV 1.0 • ISS 11APR12 

Table 7: Directional sound characteristics (vertical pattern) , per 
CAN/ULC-S525 

Angle (°) [1] 

Sound output (dBA)  

90 (Ref) 

0 (Ref)  

80 and 110 

39 and 125 

[1] Angles are measured from a perpendicular axis; positive angles are 
up. 
 

Table 8: Horn operating current in RMS (mA), continuous 

Setting High 

dB 

Low 

dB 

VDC 69.1 

41.2 

VFWR 135 

91.3 

 

Table 9: Typical current values (mA) at 24V 

Setting High 

dB 

Low 

dB 

VDC 49.0 

32.3 

VFWR 99.1 

67.1 

Regulatory information 

 
Manufacturer 

Edwards, A Division of UTC Fire & Security 
Americas Corporation, Inc. 
8985 Town Center Parkway, Bradenton, FL 
34202, USA 

Year of 
manufacture 

The first two digits of the DATE MFG number 
(located on the product identification label) are 
the year of manufacture. 

UL/ULC rating 

Regulated 24 DC and 24 FWR. 
This device was tested to the regulated 24 
DC/FWR operating voltage limits of 16 V and 
33 V. Do not apply 80% and 110% of these 
values for system operation. 

FCC compliance 

This device complies with part 15 of the FCC 
Rules. Operation is subject to the following two 
conditions: (1) This device may not cause harmful 
interference, and (2) this device must accept any 
interference received, including interference that 
may cause undesired operation. 

ICES compliance 

This Class B digital apparatus complies with 
Canadian ICES-003. 

Environmental 
class 

Indoor and outdoor 

Synchronization 

Maximum allowed resistance between any two 
devices is 20 

. Refer to specifications for 

compatible synchronization sources, this horn, 
and the control panel to determine allowed wire 
resistance. 

Agency listings 

UL 464, CAN/ULC-S525 

 

Contact information 

For contact information see www.utcfireandsecurity.com. 

FR: Feuillet d’installation 

Description 

L’avertisseur sonore pour usage extérieur Genesis WG4 est un 
appareil de notification pour la sécurité des personnes, conçu 
pour une utilisation en intérieur ou en extérieur et pour un 
montage au plafond ou sur un mur. Voir Table 1 pour une liste 
des modèles et Table 2 pour une liste des accessoires.  

Pour les applications à montage en surface, monter le WG4 
sur un boîtier électrique Model 449 à l’aide du joint livré avec 
l’appareil. Pour les applications à montage encastré où la 
surface de montage est alignée avec la surface du mur ou du 
plafond, utiliser le nécessaire de joint WG4GSKT. 

Remarque : un boîtier électrique Model 449 est nécessaire 
pour les applications étanches. Pour toutes les autres 
applications, utiliser un boîtier électrique carré de 10,16 cm 
(4 po) en montage standard. 

L’avertisseur sonore inclut des options de cavalier 
configurables sur le terrain qui permettent de régler le motif de 
l’avertisseur sur temporel ou continu et le volume de 
l’avertisseur sur faible ou élevé. 

Tableau 1 : Modèles 

Numéro Description 

WG4WF-H  

Avertisseur sonore à montage au mur ou au plafond 
pour usage extérieur, blanc avec marquage FIRE  

WG4WN-H 

Avertisseur sonore à montage au mur ou au plafond 
pour usage extérieur, blanc sans marquage  

WG4RF-H  

Avertisseur sonore à montage au mur ou au plafond 
pour usage extérieur, rouge avec marquage FIRE  

WG4RN-H 

Avertisseur sonore à montage au mur ou au plafond 
pour usage extérieur, rouge sans marquage  

Tableau 2 : Accessoires 

Numéro Description 

WG4WTS [1] 

Embase à montage en surface pour usage extérieur, 
blanche, pour avertisseur sonore Genesis WG4 ou 
avertisseur sonore/stroboscope 

WG4RTS [1] 

Embase à montage en surface pour usage extérieur, 
rouge, pour avertisseur sonore Genesis WG4 ou 
avertisseur sonore/stroboscope 

WG4GSKT [2]  Joint de rechange pour appareil, montage encastré 

[1] L’embase d’encastrement est à usage extérieur lorsqu’elle est 
utilisée avec le boîtier électrique Model 449. 
[2] Non compatible avec les embases d’encastrement. 

Pour synchroniser le fonctionnement des avertisseurs sonores, 
il est nécessaire d’installer une source de synchronisation 
distincte. Voir Table 3. Lors de la connexion de l’avertisseur 
sonore à un panneau de commande homologué, vérifier 
l’opération de synchronisation sur la liste de compatibilité pour 
le panneau en question. 

Summary of Contents for Edwards Genesis WG4 Series

Page 1: ...orn or horn strobe WG4RTS 1 Outdoor rated surface skirt red for Genesis WG4 horn or horn strobe WG4GSKT 2 Appliance replacement gasket flush mount 1 The trim skirt is outdoor rated when used with the Model 449 electrical box 2 Not compatible with the trim skirts To synchronize horn operation you must install a separate synchronization source See Table 3 When connecting the horn to a listed control...

Page 2: ... Specifications on page 3 for a list of compatible boxes 4 Feed the field wiring through the wire slots on the gasket and the backplate See Figure 2 item 3 and Figure 3 item 1 5 Align the appliance and trim skirt if applicable and then secure the backplate to the electrical box with the supplied screws Check the assembly to ensure that it is securely mounted 6 Set the horn volume The default horn ...

Page 3: ...imensions W H D 5 6 8 5 1 4 in 142 216 36 mm Sound level output See Table 4 Table 5 Table 6 and Table 7 Horn tone 3 2 kHz Wire size 12 to 18 AWG 0 75 to 2 50 mm Compatible electrical box Outdoor Indoor Model 449 4 in square by 1 5 in deep box Operating environment Temperature Relative humidity 40 to 151 F 40 to 66 C 0 to 95 noncondensing Table 4 Sound pressure level dBA per UL 464 Volume Setting 1...

Page 4: ...nd ou sur un mur Voir Table 1 pour une liste des modèles et Table 2 pour une liste des accessoires Pour les applications à montage en surface monter le WG4 sur un boîtier électrique Model 449 à l aide du joint livré avec l appareil Pour les applications à montage encastré où la surface de montage est alignée avec la surface du mur ou du plafond utiliser le nécessaire de joint WG4GSKT Remarque un b...

Page 5: ...ner le joint approprié sur la platine arrière en vérifiant que la fente de guidage des câbles et les autres orifices s alignent correctement Retirer le revêtement de protection de la surface du joint et appliquer précautionneusement le joint sur le WG4 avec le côté adhésif orienté vers l appareil L appuyer fermement contre la surface arrière de l appareil pour le positionner correctement 3 Mettre ...

Page 6: ...te de guidage des câbles et des cavaliers JP3 1 2 3 JP1 1 Fente de guidage des câbles 2 Cavalier du volume de l avertisseur sonore JP3 3 Cavalier du motif de l avertisseur sonore JP1 Câblage Voir Figure 4 Raccorder tous les fils conformément aux codes de l électricité locaux et aux exigences locales pertinentes Attention risque pour le dispositif Pour éviter d endommager le dispositif vérifier que...

Page 7: ...veau de pression sonore dBA selon UL 464 Réglage du volume 16 V 24 V 33 V Continu élevé 89 7 94 7 97 4 Continu faible 85 4 89 5 92 5 Temporel élevé 84 2 90 5 93 5 Temporel faible 81 7 85 4 88 1 dBA décibels pondérés A UL 464 niveau de sortie sonore mesuré dans une salle réverbérante à 3 05 m 10 pi Tableau 5 Niveau de pression sonore dBA selon CAN ULC S525 Réglage du volume 16 V 24 V 33 V Continu é...

Page 8: ...la partie 15 des règles FCC Son fonctionnement est soumis aux deux conditions suivantes 1 ce dispositif ne doit pas causer d interférences nuisibles et 2 il doit accepter toutes les interférences reçues y compris celles qui sont susceptibles d entraîner un fonctionnement indésirable Conformité ICES Cet appareil numérique de classe B est conforme à la norme canadienne ICES 003 Classe de service Int...

Reviews: