background image

4 / 4 

 

P/N 3101853 • REV 2.0 • ISS 21MAR11 

Table 6: Outdoor strobe output (cd) 

Lens 

Standard 

D C B A 

Clear 

UL 

1638 

41 50 60 65 

Amber 

UL 

1638 

34 41 51 52 

Table 7: UL 1638 outdoor light output 

Lens Rating 

(cd) 

Clear 

233 nominal, 65 cd at 

35°C 

Amber 

188 nominal, 52 cd at 

35°C 

Table 8: Strobe operating current in RMS (A) 

Setting 

D C B A 

VDC 324 390 494 495 

VFWR 

412 487 607 646 

 

Figure 6: UL 1971 minimum light output (% of rating vs. angle) 

1

2

20

40

60

80

100

120

140

160

180

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

- 90

- 85

- 80

- 75

- 70

- 65

- 60

- 55

- 50

- 45

- 40

- 35

- 30

- 25

- 20

- 15 - 10

- 5

 

1. Angle 
2. 

Percentage of rated output 

Note: Horizontal plot 

Regulatory information 

 
Manufacturer 

Edwards, A Division of UTC Fire & Security 
Americas Corporation, Inc. 
8985 Town Center Parkway, Bradenton, FL 
34202, USA 

Year of manufacture 

The first two digits of the DATE MFG 
number (located on the product identification 
label) are the year of manufacture. 

UL rating 

Regulated 24 DC, Regulated 24 FWR 

Synchronization 

Meets: UL 1971 requirements [1] 

North American 
standards  

Meets: UL 1971 [1], UL1638, UL1480 
Follow: NFPA 72 

FCC compliance 

This device complies with part 15 of the 
FCC Rules. Operation is subject to the 
following two conditions: (1) This device 
may not cause harmful interference, and (2) 
this device must accept any interference 
received, including interference that may 
cause undesired operation. 

Industry Canada 
compliance 

This Class A digital apparatus complies with 
Canadian ICES-003 

[1] Only models with a clear lens meet UL 1971. 

Contact information 

For contact information see: www.utcfireandsecurity.com. 

Summary of Contents for EDWARDS WG4WN-SVMHC

Page 1: ...aker strobe 25 70 V white without marking 102 123 147 161 cd clear lens 1 Only indoor strobes with a clear lens comply with the latest requirements of UL 1971 Signaling Devices for the Hearing Impaired Table 2 Accessories Number Description WG4WTS 1 Outdoor rated surface skirt white for Genesis WG4 speaker or speaker strobe WG4RTS 1 Outdoor rated surface skirt red for Genesis WG4 speaker or speake...

Page 2: ...osition the speaker voltage setting switch S3 See Figure 5 item 4 10 Set the candela output The default candela setting is D To select a different candela output align the S2 indicator to the desired candela output See Table 5 and Figure 5 item 1 11 The default wattage setting is Z corresponding to 1 4 watt To select a different wattage align the S1 indicator to the desired wattage setting See Tab...

Page 3: ...o 151 F 35 to 66 C 0 to 95 noncondensing Table 3 Compatible synchronization sources models Name Number Auto Sync Output Module SIGA CC1S GSA MCC1S GSA CC1S SIGA CC2A SIGA MCC1S SIGA MCC2A Genesis Signal Master Remote Mount ADTG1M RM MG1M RM G1M RM EG1M RM Table 4 Sound level output dBA Wattage Setting 25 V 70 V 2 W T 90 0 89 7 1 W X 87 1 86 9 1 2 W Y 84 0 83 9 1 4 W Z 80 8 80 8 dBA Decibels A weig...

Page 4: ...UTC Fire Security Americas Corporation Inc 8985 Town Center Parkway Bradenton FL 34202 USA Year of manufacture The first two digits of the DATE MFG number located on the product identification label are the year of manufacture UL rating Regulated 24 DC Regulated 24 FWR Synchronization Meets UL 1971 requirements 1 North American standards Meets UL 1971 1 UL1638 UL1480 Follow NFPA 72 FCC compliance ...

Reviews: