4 / 4
P/N 3101853 • REV 2.0 • ISS 21MAR11
Table 6: Outdoor strobe output (cd)
Lens
Standard
D C B A
Clear
UL
1638
41 50 60 65
Amber
UL
1638
34 41 51 52
Table 7: UL 1638 outdoor light output
Lens Rating
(cd)
Clear
233 nominal, 65 cd at
−
35°C
Amber
188 nominal, 52 cd at
−
35°C
Table 8: Strobe operating current in RMS (A)
Setting
D C B A
VDC 324 390 494 495
VFWR
412 487 607 646
Figure 6: UL 1971 minimum light output (% of rating vs. angle)
1
2
20
40
60
80
100
120
140
160
180
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
- 90
- 85
- 80
- 75
- 70
- 65
- 60
- 55
- 50
- 45
- 40
- 35
- 30
- 25
- 20
- 15 - 10
- 5
1. Angle
2.
Percentage of rated output
Note: Horizontal plot
Regulatory information
Manufacturer
Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA
Year of manufacture
The first two digits of the DATE MFG
number (located on the product identification
label) are the year of manufacture.
UL rating
Regulated 24 DC, Regulated 24 FWR
Synchronization
Meets: UL 1971 requirements [1]
North American
standards
Meets: UL 1971 [1], UL1638, UL1480
Follow: NFPA 72
FCC compliance
This device complies with part 15 of the
FCC Rules. Operation is subject to the
following two conditions: (1) This device
may not cause harmful interference, and (2)
this device must accept any interference
received, including interference that may
cause undesired operation.
Industry Canada
compliance
This Class A digital apparatus complies with
Canadian ICES-003
[1] Only models with a clear lens meet UL 1971.