Chapter 2: Installation
10
SynaG Series Installation Manual
Table 3: Recommended cables
Cable
Cable description
Maximum cable length
Mains cable
3 x 1.5 mm²
N/A
Zone circuit cable (mixed zone) 12 to 26 AWG (3.31 to 0.13 mm²)
Twisted-pair (max. 40
Ω
/ 500 nF)
2 km
Zone circuit cable (automatic or
manual zones)
12 to 26 AWG (3.31 to 0.13 mm²)
Twisted-pair (max. 55
Ω
/ 500 nF)
2 km
Fire network cable
Twisted-pair, Cat 5
12 to 26 AWG (3.31 to 0.13 mm²)
1.2 km
Note:
Other types of cable may be used subject to site-specific EMI conditions
and installation testing.
Use 20 mm cable glands to ensure clean and secure connections at the control
panel cabinet. All cables should be fed through the cable guides in the cabinet
housing to eliminate movement.
Overview of fire system connections
Standard, EN 54-13, BS 5839-1, and intrinsically-safe fire system connections
are shown in the following figures.
Figure 4: Standard fire system connections (no EN 54-13 requirement)