background image

 

SynaG Series Installation Manual 

Chapter 1

 

Introduction

 

Summary 

This chapter provides an introduction to your control panel and the available 
operating modes. 

Content 

Product range   2

 

Product compatibility   2

 

Operating modes   3

 

 

Summary of Contents for Kidde AirSense SynaG Series

Page 1: ...SynaG Series Installation Manual P N 501 435003 1 10 REV 1 0 ISS 14OCT11 ...

Page 2: ... with the essential requirements and other relevant provisions of Directive 1999 5 EC 2002 96 EC WEEE directive Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or dispose of it at designated collection points For more information see...

Page 3: ... board configuration 51 Fire network and repeaters configuration 53 Commissioning 59 Chapter 4 Maintenance 63 Fire alarm system maintenance 64 Battery maintenance 64 Chapter 5 Technical specifications 67 Zone specifications 68 Input and output specifications 69 Power supply specifications 71 Mechanical and environmental specifications 72 Fire network specifications 73 Cabinet drawings and dimensio...

Page 4: ... of life Caution Caution messages advise you of possible equipment damage They tell you which actions to take or to avoid in order to prevent the damage Note Note messages advise you of the possible loss of time or effort They describe how to avoid the loss Notes are also used to point out important information that you should read Limitation of liability To the maximum extent permitted by applica...

Page 5: ...this manual applicable codes and the instructions of the authority having jurisdiction is mandatory While every precaution has been taken during the preparation of this manual to ensure the accuracy of its contents UTCFS assumes no responsibility for errors or omissions ...

Page 6: ...iv SynaG Series Installation Manual ...

Page 7: ... Installation Manual 1 Chapter 1 Introduction Summary This chapter provides an introduction to your control panel and the available operating modes Content Product range 2 Product compatibility 2 Operating modes 3 ...

Page 8: ...panel with Scandinavian key switch SG8000 SynaG 8 Zone conventional control panel SG8000SC SynaG 8 Zone conventional control panel with Scandinavian key switch All models have been designed in accordance with EN 54 2 EN 54 4 BS 5839 1 NBN S 21 100 and NEN 2535 standards For further details see Appendix B Product compliance on page 91 Product compatibility Products compatible with this control pane...

Page 9: ...n EN 54 2 default Yes European Union EN 54 2 Evacuation Yes European Union Spain EN 54 2 Scandinavia Yes European Union Scandinavia BS 5839 1 No 2nd stage No United Kingdom BS 5839 1 2nd stage No United Kingdom NBN S 21 100 Yes Belgium NEN 2535 2 Yes The Netherlands 1 EN 54 13 supervision requires compatible system wiring and devices and must be enabled by the installer in the control panel config...

Page 10: ...Chapter 1 Introduction 4 SynaG Series Installation Manual ...

Page 11: ...for two and four zone control panels 6 Cabinet layout for eight zone control panels 7 Cabinet installation 8 Preparing the cabinet 8 Where to install the cabinet 8 Fixing the cabinet to the wall 8 Connections 9 Recommended cables 9 Overview of fire system connections 10 Connecting zones and zone devices 12 Connecting inputs 14 Connecting supervised outputs 16 Connecting the mains power supply 18 S...

Page 12: ...display 2 Zone and fire system connectors 3 Cable knockouts 4 Mounting screw knockouts 5 Network board connector on the back of the PCB 6 Battery area 7 Key connector 8 Alarm counter connector 9 Power supply unit 10 Power supply connector 11 Battery connector 12 Expansion board connector 13 Cable holder 14 Fuse terminal block Note Only selected regional models have the key and alarm counter connec...

Page 13: ...ne and system connectors 3 Cable knockouts 4 Mounting screw knockouts 5 Network board connector on the back of the PCB 6 Battery area 7 Power supply unit 8 Key connector 9 Alarm counter connector 10 Fuse terminal block 11 Power supply connector 12 Battery connector 13 Expansion board connector 14 Cable holder Note Only selected regional models have the key and alarm counter connectors ...

Page 14: ...age 67 for more information on the operating temperature and relative humidity specifications Allow for enough floor and wall space so the panel can be installed and serviced without any obstructions The cabinet should be mounted so that the user interface is at eye level Note that the control panel must be assembled and installed according to the ordinances and codes that are in effect in your ma...

Page 15: ...into each 3 Insert screw 1 half way and hang the cabinet onto this screw 4 Insert screws 2 and tighten 5 Insert screws 3 and tighten 6 Tighten screw 1 Connections WARNING Electrocution hazard To avoid personal injury or death from electrocution do not make any control panel or system connections while the control panel is connected to the mains power supply Recommended cables Recommended cables fo...

Page 16: ...twork cable Twisted pair Cat 5 12 to 26 AWG 3 31 to 0 13 mm 1 2 km Note Other types of cable may be used subject to site specific EMI conditions and installation testing Use 20 mm cable glands to ensure clean and secure connections at the control panel cabinet All cables should be fed through the cable guides in the cabinet housing to eliminate movement Overview of fire system connections Standard...

Page 17: ...naG Series Installation Manual 11 Figure 5 EN 54 13 fire system connections Figure 6 BS 5839 1 fire system connections 1 A diode must be connected on the detector base Consult your detector installation manual for more details ...

Page 18: ...ce Zone type Line resistance Standard and BS5839 1 EN 54 13 and intrinsically safe Mixed 40 Ω max Not supported 1 Automatic 55 Ω max 50 Ω max Manual 55 Ω max 50 Ω max 1 Mixed zones are not permitted in installations requiring EN 54 13 or intrinsically safe configuration To measure the line resistance 1 Create a short circuit at the end of the zone line 2 Measure the resistance between the positive...

Page 19: ...n page 10 The panel supports conventional detectors To guarantee optimal operation use the detectors specified in the compatibility list For more information on fire detectors see Chapter 5 Technical specifications on page 67 Connecting manual call points Connect manual call points in parallel as shown in Figure 4 Figure 5 Figure 6 and Figure 7 starting on page 10 Each zone circuit can support up ...

Page 20: ... Extended fire routing delay 2 Delays off BS 5839 1 1 Class change Delays off NBN S 21 100 1 Remote reset Delays off NEN 2535 EN 54 13 disabled Fire routing inhibit delay Delays off NEN 2535 EN 54 13 enabled Fire routing acknowledgement type 1 100 seconds 3 Fault warning output open supervision 1 No change to input functionality with EN 54 13 enabled 2 Remote reset for two zone control panels oper...

Page 21: ...conds 1 220 Ω Short circuit 220 Ω to 8 kΩ Active 2 8 kΩ to 10 kΩ Fault 3 10 kΩ to 20 kΩ Standby 20 kΩ Open circuit 1 Values between each state may vary depending on tolerance 2 For EN 54 13 compliance the active impedance should be in the range of 220 Ω to 3 9 kΩ 3 High impedance fault Table 10 Nominal resistance values for fault warning output open supervision inputs Input function Standby Fault ...

Page 22: ...tions requiring EN 54 13 compliance For more information see EN 54 13 supervision mode on page 34 Output functionality The function of each output is defined by the panel operating mode and output class configuration the default is Class B All outputs are overload protected Table 12 Class B output functionality default Operating mode OUT1 OUT2 OUT3 OUT4 EN 54 2 Sounders Sounders Sounders Fire rout...

Page 23: ...see Figure 5 on page 11 See Input and output specifications on page 69 for details on voltage and current ratings Output polarity All outputs are polarity sensitive Observe polarity or install a 1N4007 diode or equivalent to avoid inverted activation issues Connecting sounders or other notification devices to supervised outputs Depending on the operating mode up to four sounder or notification dev...

Page 24: ...onnectors 3 2010 1 SB expansion board connectors Connecting the mains power supply Note To avoid unwanted arcing connect the mains power supply before connecting the batteries The control panel can be operated at 110 V at 60 Hz or 240 V at 50 Hz 10 15 Mains power should be sourced directly from a separate circuit breaker in the building electrical supply distribution board This circuit should be c...

Page 25: ...nt Power switching for 115 or 230 VAC operation is automatic for two and four zone control panels and no configuration is required For eight zone control panels the default power setting is 230 VAC For 115 VAC operation use a small screwdriver to change the power setting switch located on the side of the power supply unit as shown in Figure 11 below Caution Risk of equipment damage An incorrect po...

Page 26: ...ent 24 VDC auxiliary output Connect auxiliary equipment that requires 24 VDC power to the 24 AUX terminals as shown in Figure 4 on page 10 The 24 VDC auxiliary output is supervised for short circuit and voltage output level WARNING Never use the auxiliary output to power expansion boards connected to the same control panel as this might damage the control panel hardware Connecting alarm and fault ...

Page 27: ...nstallation Sheet for detailed installation and connection information Each 2010 1 NB network board has two ports Each port is connected point to point to the corresponding ports of the network board in another control panel Figure 13 Network board connections Two wiring options are possible Ring configuration Bus configuration Ring configuration Ring network configuration is recommended as it pro...

Page 28: ...onfiguration only in cases where the detection zones and mandatory EN 54 2 output functions sounder and fire routing outputs are not remote between panels Bus network configuration is not normally recommended as it does not provide for redundancy in the transmission path For bus configuration Class B connect control panels as shown below Figure 15 Fire network bus configuration ...

Page 29: ...ontrol panels 26 User levels 27 Configuration overview 28 Configuration controls 28 Common configuration tasks 30 Basic configuration 31 The basic configuration menu 31 Basic default configuration 33 EN 54 13 supervision mode 34 Panel mode 34 Sounder delay 35 Fire routing delay 37 Extended fire routing delay 38 Adding expansion boards 39 Adding a fire network board 39 Advanced configuration 39 The...

Page 30: ...ration and serial number information 50 Expansion board configuration 51 Adding an expansion board 51 Expansion board configuration 52 Fire network and repeaters configuration 53 Basic configuration options 54 Advanced configuration options 55 Commissioning 59 Before commissioning the control panel 59 Commissioning the control panel 60 Functional tests 61 Response times 61 ...

Page 31: ...ounder Delay button and LED 2 7 Networking Fault LED 8 Reserved for special use 2 9 Expansion I O Fault Disabled LED 10 General Disable button and LED 11 General Test button and LED 12 Configuration controls 13 Reset button and LED 14 Panel Silence button and LED 15 Sounder Start Stop button and LED 16 System Fault LED 17 Out of Service LED 18 Earth Fault LED 19 Supply Fault LED 20 Fire Routing De...

Page 32: ...ecial use 2 9 Expansion I O Fault Disabled LED 10 General Disable button and LED 11 General Test button and LED 12 Configuration controls 13 Reset button and LED 14 Panel Silence button and LED 15 Sounder Start Stop button and LED 16 System Fault LED 17 Out of Service LED 18 Earth Fault LED 19 Supply Fault LED 20 Fire Routing Delay button and LED 2 21 Fire Routing ON ACK and Fault Disable Test but...

Page 33: ...guration Public user The public user level is the default user level This level allows basic operating tasks such as responding to fire alarms extinguishing events or fault warnings at the control panel No password is required Operator user The operator user level allows additional operating tasks that command the system or perform maintenance functions It is reserved for authorized users who have...

Page 34: ...one type then the seven segment display defaults to the custom display operating mode See Panel mode on page 34 for details Configuration overview To facilitate rapid configuration of the most common tasks configuration is divided into basic and advanced levels For basic configuration options see Basic configuration on page 31 For advanced configuration options see Advanced configuration on page 3...

Page 35: ...a menu selection or a value selection entry 1 1 Panels configured as repeaters in a fire network normally display the status of several panels Pressing this button for 3 seconds provides a temporary display of local panel status The seven segment display The seven segment display is only visible when the control panel cover is removed see Figure 1 on page 6 and Figure 2 on page 7 Figure 19 The sev...

Page 36: ... Press Enter When a configuration menu has been selected the Value LED on the seven segment display is steady To select a value 1 Select the required value using the value selection buttons 2 and 4 2 Press Enter To exit configuration mode and save your changes 1 Press Panel Silence 2 Press Enter or 1 Set the display as shown below and then press Enter The Panel Silence LED flashes to confirm that ...

Page 37: ...play as shown below and then press Enter To restore the factory configuration 1 Set the display as shown below and then press Enter Basic configuration The default password for basic configuration is 3333 After entering the password the first displayed menu will be Basic default configuration indicating basic installer user level For more information see User level passwords and indications on pag...

Page 38: ...d fire routing delay 00 to 10 minutes EN 54 2 EN 54 2 Scandinavia NEN 2535 Add an expansion board 1 00 to 04 modules All Fire network identifier 2 00 to 32 All Restore previous configuration N A All Restore factory configuration N A All Exit without saving N A All Exit and save N A All 1 Additional menu options are available if one or more expansion boards are installed See Expansion board configu...

Page 39: ...mode configuration presets EN 54 13 disabled Display Operating mode Zone end of line Zone type 01 default EN 54 2 Passive Mixed 05 EN 54 2 Evacuation Passive Mixed 07 EN 54 2 Scandinavia Passive Mixed 11 BS 5839 1 Active Mixed 21 NBN S 21 100 Passive Odd zones Automatic Even zones Manual 31 NEN 2535 Passive Odd zones Automatic Even zones Manual The operating mode is indicated by the first digit in...

Page 40: ...icate that the supervision mode configuration menu is active 2 Select the supervision mode using the value selection buttons 2 and 4 3 Press Enter 4 Save your changes The available settings for this feature are shown below Display Description Default setting EN 54 13 zone supervision is disabled and all outputs are configured as Class B EN 54 13 zone supervision is enabled and all outputs are conf...

Page 41: ... indicated if any of the following zone configuration settings are changed from the operating mode preset values Zone delay Zone configuration Zone type Input configuration The seven segment display will alternate the custom and base operating mode indications as shown above Sounder delay Note Use this menu to configure evacuation sounder delays in NBN S 21 100 mode Use this menu to configure a so...

Page 42: ...ured the delay must be enabled at Operator user level To enable a configured delay 1 Exit Installer user level 2 Enter the Operator user level password 3 Press the Sounder Delay button A steady Sounder Delay LED indicates that the delay is enabled Sounder outputs delay operation The delay applies to the activation of sounder outputs only if all of the following are true The delay is enabled The in...

Page 43: ...535 01 EN 54 2 NBN S 21 100 00 EN 54 2 Evacuation BS 5839 1 This feature is not available in these operating modes To configure a delay 1 Set the display as shown below and then press Enter The Fire Routing Delay LED flashes fast to indicate that the fire routing delay configuration menu is active 2 Select a delay value from 00 to 10 minutes using the value selection buttons 2 and 4 3 Press Enter ...

Page 44: ... after the detection of the fire alarm Extended fire routing delay Use this menu to configure an extended fire routing delay of up to 10 minutes in operating modes where the feature is available Default delays The default extended fire routing delay for each operating mode is shown below Table 24 Extended fire routing delay default values Operating mode Default delay in minutes EN 54 2 Scandinavia...

Page 45: ...comes the active delay to activate fire routing when sounders are stopped by pressing the Sounder Start Stop button and remain stopped when the standard fire routing delay time has elapsed In EN 54 2 NEN 2535 and EN 54 2 Scandinavia operating mode the extended fire routing delay becomes the active delay to activate fire routing when an extended fire routing delay switch connected to an input confi...

Page 46: ...4 13 supervision ON OFF EN 54 2 EN 54 2 Evacuation EN 54 2 Scandinavia NBN S 21 100 NEN 2535 Custom Panel mode EN 54 2 EN 54 2 Evacuation EN 54 2 Scandinavia BS 5839 1 No 2nd stage BS 5839 1 2nd stage NBN S 21 100 NEN 2535 Custom All Sounder delay or Evacuation sounder delay for NBN S 21 100 mode 00 to 10 minutes EN 54 2 EN 54 2 Evacuation EN 54 2 Scandinavia NBN S 21 100 Sounder operation during ...

Page 47: ... Passive EOL with CleanMe Active EOL with CleanMe Intrinsically safe All Zone delay ON OFF All Zone type Mixed Automatic Manual All Input configuration Remote reset Delays off Fire routing extended delay Fire routing inhibit delay Class change Fault warning output open supervision NEN 2535 only Fire routing acknowledgement type 1 100 seconds Fire routing acknowledgement type 2 240 seconds FBF inte...

Page 48: ...ation during a zone test The default setting for all operating modes is ON To configure the sounder operation during a zone test 1 Set the display as shown below and then press Enter The Sounders Start Stop LED flashes fast to indicate that the sounder operation during a zone test configuration menu is active 2 Select a value using the value selection buttons 2 and 4 3 Press Enter 4 Save your chan...

Page 49: ...s reported from a different zone The sounders do not re sound if a new fire alarm event is reported from a different zone Note For new fire alarm events in the same zone sounders will always re sound if the first alarm is reported by a detector and the new alarm is reported by a manual call point Sounders silence disabled time Note For control panels in basic evacuation mode any configured fire so...

Page 50: ... The Sounders Start Stop LED flashes fast to indicate that the Sounders Silence Disabled Time configuration menu is active 2 Select a delay value from 1 to 10 minutes using the value selection buttons 2 and 4 3 Press Enter 4 Save your changes Zone configuration Use this menu to configure zone settings for each zone in your fire alarm system The default setting for each operating mode is included i...

Page 51: ...lay is ON for alarms reported from this zone any output activation sounders fire routing and expansion board outputs will consider delay before activation The default setting for all zones is ON For a stand alone fire panel you specify the zone using the zone number When the control panel is in a fire network unique zone numbers are created by defining a unique starting number for the first zone i...

Page 52: ... delays are not applied Outputs activate immediately when the alarm is reported from this zone Zone type Use this menu to configure the zone type for each zone in your fire alarm system The default setting for each operating mode is included in Appendix A Configuration presets on page 79 To configure the zone type 1 Set the display as shown below and then press Enter 2 Select the zone for example ...

Page 53: ...ilable if EN 54 13 is enabled or an intrinsically safe zone is configured Input configuration Use this menu to configure the functionality of INPUT1 and INPUT2 The default setting for each input is included in Appendix A Configuration presets on page 79 To configure an input 1 Set the display as shown below and then press Enter 2 Select the input for example INPUT1 and then press Enter 3 Select a ...

Page 54: ...a fire routing fault EN 54 2 EN 54 2 Scandinavian NEN 2535 Fire routing acknowledgement type 2 240 seconds 1 3 An active input indicates acknowledge after fire routing is active An active input in other condition generates a fire routing fault EN 54 2 EN 54 2 Scandinavian NEN 2535 FBF interface sounders disabled 2 3 Active input disables sounders and silences the control panel EN 54 2 EN 54 2 Evac...

Page 55: ...ssword and then press Enter 2 Set the display as shown below and then press Enter 3 Select a value using the value selection buttons 2 and 4 4 Press Enter 5 Save your changes Auxiliary 24 V reset Use this menu to configure the auxiliary 24 V reset setting on or off The default setting is OFF To configure the 24 V reset 1 Set the display as shown below and then press Enter 2 Select a value using th...

Page 56: ...ork board The following submenus are available for software version and serial number menus Display Description Display the software version or serial number for the control panel Display the software version or serial number for expansion board A Display the software version or serial number for expansion board B Display the software version or serial number for expansion board C Display the soft...

Page 57: ...ed expansion boards The default value is 00 To add an expansion board 1 Set the display as shown below and then press Enter The Expansion I O Fault Disabled LED flashes fast to indicate that the module configuration menu is active 2 Select a value using the value selection buttons 2 and 4 3 Press Enter 4 Save your changes The maximum number of expansion boards that can be installed is shown below ...

Page 58: ...n menus Note These configuration options are repeated for each of the installed expansion boards A B C and D Table 27 Expansion board A configuration options Display Description Value Module A function 01 to 92 1 Module A output 1 delay 00 to 10 minutes Module A output 2 delay 00 to 10 minutes Module A output 3 delay 00 to 10 minutes Module A output 4 delay 00 to 10 minutes 1 Available values depe...

Page 59: ...he module delay menu is active 2 Select a value from 00 to 10 using the value selection buttons 2 and 4 3 Press Enter 4 Repeat steps 1 to 3 as required for each output 1 to 4 on each installed module A B C and D where a delay is required 5 Save your changes Fire network and repeaters configuration This section describes how to configure a fire network of conventional control panels in order to Con...

Page 60: ...its of the number positions 3 and 4 or Firenet initial panel number to be repeated 2 01 to 32 Default 01 1 Basic configuration uses consecutive numbers beginning with 1 and ending with the number entered here Advanced configuration allows the use of specific nonsequential node numbers When the system has an advanced custom pattern of node numbers the displayed value for nn is Cu 2 Depending on the...

Page 61: ...etting if you want to keep activations and indications independent in different control panels Example In a 16 zone virtual panel eight zone panel 1 can keep initial zone with the default value 1 and the eight zone panel 2 requires changing initial zone from 1 to 9 Note that this setting can be used to configure control panels to repeat the status of control panels in the fire network with the zon...

Page 62: ...et repeater type nr Pn 01 to 32 Default 01 Firenet global controls On OFF Default On Firenet loop class A B Default B Firenet process remote zones On OFF Default On Firenet repeater type 2n Zones Repeater Pn Panels Repeater Default 2n Firenet map Submenu 1 32 Values On OFF Default ON for nodes 1 and 2 OFF for the rest Firenet repeater map Submenu 1 32 Values On OFF Default ON for nodes 1 and 2 OFF...

Page 63: ...des 1 and 2 Panel ID 20 with nM active for nodes 20 and 32 Panel ID 32 with nM active for nodes 20 and 32 Panels 1 and 2 will see each other in one sub network and panels 20 and 32 will see each other in a different sub network Only a firenet wiring open loop fault for class A networks will be shared between the two sub networks Repeater map rM configuration Any control panel in the fire network c...

Page 64: ... fire protection Examples If we disable zone 1 in control panel 1 and control panel 1 repeats control panel 2 the zone 1 in control panel 2 will also be disabled shared zone completely disabled If we disable zone 1 in control panel 1 but control panel 2 is not repeated zone 1 in panel 2 will not be disabled This allows disabling only part of the shared zone Selecting the loop class Select the loop...

Page 65: ...ration utility software if you require this type of advanced configuration If the control panel is configured for remote output control it will no longer activate outputs based on its own logic and will only activate outputs with commands coming from the fire network This mode of operation is fail safe i e if the control panel detects a fire network fault the outputs will activate with the local l...

Page 66: ... up Normal startup After starting up the control panel normal status standby is indicated as follows The Supply LED is steady The Sounder Delay LED is steady if a delay has been enabled The Fire Routing Delay LED is steady if a delay has been enabled If any other indicators are on check your installation thoroughly before proceeding Fault startup In accordance with EN 54 2 the control panel has a ...

Page 67: ...te alarm notification devices and fire routing where applicable immediately Activate a detector to test automatic alarm reporting The control panel should initiate any configured delays and activate alarm notification devices and fire routing where applicable once the delay time has elapsed Using a multimeter verify that the fault relay is activated when a fault is reported and that the alarm rela...

Page 68: ...econds Earth fault Less than 100 seconds Battery charger fault Less than 100 seconds No batteries found fault Less than 3 minutes Mains fault Less than 3 minutes Out of service fault Less than 100 seconds Fuse protection fault Less than 3 minutes System fault Less than 100 seconds Battery high resistance fault Less than 4 hours ...

Page 69: ...intenance Summary This chapter includes information on fire alarm system maintenance and battery maintenance Content Fire alarm system maintenance 64 Quarterly maintenance 64 Annual maintenance 64 Cleaning the control panel 64 Battery maintenance 64 ...

Page 70: ...cted to make sure that they are securely fastened that they have not been damaged and that they are appropriately protected Cleaning the control panel Keep the outside and inside of the control panel clean Carry out periodic cleaning using a damp cloth for the outside Do not use products containing solvents to clean the control panel Do not clean the inside of the cabinet with liquid products Batt...

Page 71: ...on and all connections are correct then the batteries should be replaced immediately Replacing batteries Batteries must be replaced periodically as recommended by the battery manufacturer The useful life of the battery is approximately four years Avoid the total discharge of the batteries Always use the recommended replacement batteries To replace the batteries 1 Disconnect and remove the existing...

Page 72: ...Chapter 4 Maintenance 66 SynaG Series Installation Manual ...

Page 73: ...chapter includes technical specifications for your fire alarm control panel Content Zone specifications 68 Input and output specifications 69 Power supply specifications 71 Mechanical and environmental specifications 72 Fire network specifications 73 Cabinet drawings and dimensions 74 ...

Page 74: ...Other detectors 1 32 max 32 max 2 3 Number of manual call points per zone circuit 32 max 4 1 Systems using other detectors are not EN 54 13 compliant 2 Or as defined by local standards Maximum of 30 detectors for NBN S 21 100 installations 3 Provided that the detectors meet the required zone specifications given here 4 Figures based on EN 54 2 The maximum number of devices may differ for other sta...

Page 75: ...e impedance 3 to 14 V 75 to 680 Ω 3 1 to 16 9 V 90 to 900 Ω 12 8 to 17 V 160 to 900 Ω Short circuit reference range Zone voltage Zone impedance 3 V 55 Ω 3 1V 50 Ω 11 9 V 80 Ω Open circuit reference range Zone impedance Zone device current draw Zone voltage 8 kΩ 2 6 mA 20 6 to 23 5 V N A N A 19 2 to 23 5 V 11 kΩ 1 81 mA 21 3 V High impedance fault N A 16 9 to 17 2 V N A 1 Values are referenced to t...

Page 76: ...dby EN 54 13 disabled Voltage in standby EN 54 13 enabled Voltage in alarm For open and short circuit 250 mA max 500 mA max at 25ºC 385 mA max at 40ºC 11 5 VDC max 8 4 VDC max 28 VDC max Fire routing outputs 1 Supervised Current per output four zone Current per output eight zone Voltage in standby EN 54 13 disabled Voltage in standby EN 54 13 enabled Voltage in alarm For open and short circuit 250...

Page 77: ... and four zone control panels DC voltage Rated current Current range Rated power Voltage tolerance 24 V 2 A 0 to 2 A 50 W 2 Eight zone control panel DC voltage Rated current Current range Rated power Voltage tolerance 24 V 4 A 0 to 4 A 100 W 2 Table 38 Batteries and battery charger specifications Batteries Two and four zone control panels Eight zone control panel 2 x 7 2 Ah 2 x 7 2 Ah or 2 x 12 Ah...

Page 78: ... specifications Table 40 Mechanical specifications Cabinet dimensions no cover Two and four zone control panels Eight zone control panel 300 97 402 mm 421 100 447 mm Weight without batteries Two and four zone control panels Eight zone control panel 2 8 kg 3 9 kg Number of cable knockouts Two and four zone control panels Eight zone control panel 14 x Ø 20 mm at top of cabinet 2 x Ø 20 mm at bottom ...

Page 79: ...s Installation Manual 73 Fire network specifications Table 42 Fire network specifications Maximum distance between control panels 1 2 km Maximum capacity 32 nodes and 64 zones Communication protocol Proprietary peer to peer protocol based on RS 485 ...

Page 80: ...Chapter 5 Technical specifications 74 SynaG Series Installation Manual Cabinet drawings and dimensions Figure 21 Two and four zone cabinet with cover ...

Page 81: ...Chapter 5 Technical specifications SynaG Series Installation Manual 75 Figure 22 Two and four zone cabinet without cover ...

Page 82: ...Chapter 5 Technical specifications 76 SynaG Series Installation Manual Figure 23 Eight zone cabinet with cover ...

Page 83: ...Chapter 5 Technical specifications SynaG Series Installation Manual 77 Figure 24 Eight zone cabinet without cover ...

Page 84: ...Chapter 5 Technical specifications 78 SynaG Series Installation Manual ...

Page 85: ...mary This appendix includes detailed information on operating mode and expansion board configuration presets Content Operating mode presets 80 EN 54 2 presets 80 EN 54 2 Evacuation 81 EN 54 2 Scandinavia 82 BS 5839 1 83 NBN S 21 100 84 NEN 2535 85 Expansion board presets 86 ...

Page 86: ...pervision Class A 1 1 Odd Automatic Even Manual 1 The CleanMe feature is available only with Aritech detectors Table 44 Additional configuration characteristics Default sounder delay 0 Default fire routing delay 0 Default extended fire routing delay 0 Default zone delay 0n Start Restart sounders Start sounders only if there is a fire alarm Sounders Silence Disabled Time 1 minute Table 45 Inputs an...

Page 87: ...54 13 supervision Class A 2 Odd Automatic Even Manual 1 The CleanMe feature is available only with Aritech detectors Table 47 Additional configuration characteristics Default sounder delay 0 Default zone delay 0n Start Restart sounders Start sounders or restart stopped sounders at user level 2 with fire alarm event Table 48 Inputs and outputs Input Output Standard EN 54 13 INPUT1 Remote reset Remo...

Page 88: ...ech detectors Table 50 Additional configuration characteristics Default sounder delay 0 Default fire routing delay 1 Default extended fire routing delay 3 Default zone delay 0n Start Restart sounders Start sounders or restart stopped sounders at Operator user level with or without a fire alarm event Table 51 Inputs and outputs Input Output Standard EN 54 13 INPUT1 Two zone control panel Remote res...

Page 89: ...vacuation Mixed 14 Four zone eight zone Active CleanMe enabled 2 Class B 4 stage 2 Evacuation Mixed 1 Stage 1 Alert sounders off during any configured sounder delay Stage 2 Evacuation sounders intermittent during any configured sounder delay 2 The CleanMe feature is available only with Aritech detectors Table 53 Additional configuration characteristics Default sounder delay 0 Default zone delay 0n...

Page 90: ...CleanMe feature is available only with Aritech detectors Table 56 Additional configuration characteristics Default sounder delay 0 minutes Default zone delay ON Start Restart sounders Start sounders or restart stopped sounders at user level 2 with or without a fire alarm event Table 57 Inputs and outputs Input Output Standard EN 54 13 INPUT1 Remote reset Remote reset INPUT2 Delays off Delays off O...

Page 91: ...fire routing delay 3 minutes Default zone delay ON Start Restart sounders Start sounders only if there is a fire alarm Table 60 Inputs and outputs Input Output Standard EN 54 13 INPUT1 Fire routing inhibit delay Fire routing acknowledgement type 1 100 seconds INPUT2 Delays off Fault warning output open supervision OUT1 Sounder circuit Sounder circuit OUT2 Sounder circuit OUT3 Fire routing automati...

Page 92: ... 4 Yes 7 and 8 4 Yes 02 5 1 Yes 17 1 2 3 or 4 1 Yes 6 2 Yes 2 Yes 7 3 Yes 5 6 7 or 8 3 Yes 8 4 Yes 4 Yes 05 1 1 Yes 18 1 and 2 1 Yes 2 Yes 2 Yes 2 3 Yes 3 and 4 3 Yes 4 Yes 4 Yes 06 3 1 Yes 19 5 and 6 1 Yes 2 Yes 2 Yes 4 3 Yes 7 and 8 3 Yes 4 Yes 4 Yes 07 5 1 Yes 20 1 or 2 1 Yes 2 Yes 2 Yes 6 3 Yes 3 or 4 3 Yes 4 Yes 4 Yes 08 7 1 Yes 21 5 or 6 1 Yes 2 Yes 2 Yes 8 3 Yes 7 or 8 3 Yes 4 Yes 4 Yes 13 ...

Page 93: ...on 3 No Remote RB SBx 02 output activation 4 2 No Reset on 4 No Remote RB SBx 02 output activation 4 2 No 32 2 Fire protection 1 No Remote RB SBx 04 output activation 4 4 No 2 No Fault warning output 3 3 No Fault 1 4 No 1 Fail safe mode output is active when there is no fault 2 These presets are only available for 2010 1 SB supervised expansion boards 3 NEN 2535 only Fault warning output open supe...

Page 94: ...EN 54 13 supervision enabled Display Zone Outputs Delay Display Zone Outputs Delay 05 1 1 and 2 Yes 18 1 and 2 1 and 2 Yes 2 3 and 4 Yes 3 and 4 3 and 4 Yes 06 3 1 and 2 Yes 19 5 and 6 1 and 2 Yes 4 3 and 4 Yes 7 and 8 3 and 4 Yes 07 5 1 and 2 Yes 20 1 or 2 1 and 2 Yes 6 3 and 4 Yes 3 or 4 3 and 4 Yes 08 7 1 and 2 Yes 21 5 or 6 1 and 2 Yes 8 3 and 4 Yes 7 or 8 3 and 4 Yes 17 1 2 3 or 4 1 and 2 Yes...

Page 95: ...ervised expansion boards 3 NEN 2535 only Fault warning output open supervision subject to input configuration 4 RB SBx is the expansion board x For two zone and four zone panels x can be 1 or 2 For 8 zone and evacuation panels x can be 1 2 3 or 4 Configuration 36 is only possible when the Network Remote Output Control option nO is set and it is then configured by default 5 Not compliant to EN 54 1...

Page 96: ...Appendix A Configuration presets 90 SynaG Series Installation Manual ...

Page 97: ...s Installation Manual 91 Appendix B Product compliance Summary This appendix contains regulatory information that applies to your control panel Content European standards 92 Construction Products Directive CPD 93 ...

Page 98: ...protection equipment type A 1 2 7 11 Delays to outputs 7 13 Alarm counter 3 8 4 Total loss of the power supply 8 9 Output to fault warning routing equipment 1 2 10 Test condition 1 Excluding two zone models 2 NEN 2535 operating mode only 3 Dutch models only European standards for electrical safety and electromagnetic compatibility These control panels have been designed in accordance with the foll...

Page 99: ...832 CPD 1746 0832 CPD 1747 Year of manufacture The year and day of manufacture in the format YYDDD is included in the first five digits of your product serial number located on the product identification label Manufacturer UTC Fire Security Africa 555 Voortrekker Road Maitland Cape Town 7405 PO Box 181 Maitland South Africa Authorized EU manufacturing representative Kidde Products Ltd Thame Park R...

Page 100: ...Appendix B Product compliance 94 SynaG Series Installation Manual ...

Page 101: ... 21 connecting alarm and fault relays 20 connecting detectors 13 connecting expansion boards 21 connecting fire routing equipment to supervised outputs 17 connecting inputs 14 connecting manual call points 13 connecting sounders or other notification devices to supervised outputs 17 connecting supervised inputs 15 connecting supervised outputs 16 connecting the batteries 19 connecting the fault wa...

Page 102: ...ng batteries 65 response times 61 ring configuration 21 S select remote output control 59 selecting 115 or 230 VAC operation 19 selecting control panel commands 58 selecting processing for remote zones in alarm 58 selecting the loop class 58 seven segment display 29 software compatibility ii software configuration and serial number information 50 sounder delay 35 sounder operation during a zone te...

Page 103: ......

Page 104: ......

Reviews: