Chapter 5: Technical specifications
SynaG Series Installation Manual
71
Power supply specifications
Table 36: Mains supply specifications
Operating voltage
110 VAC / 60 Hz or 240 VAC / 50 Hz
Rated current (two- and four-zone control
panels)
110
VAC
240
VAC
2 A
2 A
Rated current (eight-zone control panels)
110
VAC
240
VAC
3.15 A
1.5 A
Voltage tolerance
+10% /
−
15%
Mains fuse
110
VAC
240
VAC
T 3.15A 250V
T 2A 250V
Table 37: 24 VDC power supply specifications
Two- and four-zone control panels
DC
voltage
Rated
current
Current
range
Rated
power
Voltage
tolerance
24 V
2 A
0 to 2 A
50 W
±2%
Eight-zone control panel
DC
voltage
Rated
current
Current
range
Rated
power
Voltage
tolerance
24 V
4 A
0 to 4 A
100 W
±2%
Table 38: Batteries and battery charger specifications
Batteries
Two- and four-zone control panels
Eight-zone
control
panel
2 x 7.2 Ah
2 x 7.2 Ah or 2 x 12 Ah
Battery type
Sealed lead-acid
Battery charger voltage
27.3 V at 20ºC
−
36mV/ºC
Battery charger current
Two- and four-zone control panels
Eight-zone
control
panel
Max. 0.5 A
Max. 0.7 A
Out of service voltage level
< 22.75 V
No operation voltage level
< 21 V
Summary of Contents for Kidde AirSense SynaG Series
Page 1: ...SynaG Series Installation Manual P N 501 435003 1 10 REV 1 0 ISS 14OCT11 ...
Page 6: ...iv SynaG Series Installation Manual ...
Page 10: ...Chapter 1 Introduction 4 SynaG Series Installation Manual ...
Page 72: ...Chapter 4 Maintenance 66 SynaG Series Installation Manual ...
Page 84: ...Chapter 5 Technical specifications 78 SynaG Series Installation Manual ...
Page 96: ...Appendix A Configuration presets 90 SynaG Series Installation Manual ...
Page 100: ...Appendix B Product compliance 94 SynaG Series Installation Manual ...
Page 103: ......
Page 104: ......