Chapter 3: Configuration and commissioning
32
ZP1-X3E Series Installation Manual
Display
Menu
Values
Restore previous configuration
N/A
Restore factory configuration
N/A
Exit without saving
N/A
Exit and save
N/A
[1] Additional menu options are available if one or more expansion boards are installed. See
“Expansion board configuration” on page 60.
[2] Additional menu options are available if Firenet is configured. See “Fire network and repeaters
configuration” on page 62.
Basic default configuration
Use this menu to select operating mode configuration presets.
In both basic standard and basic evacuation modes, zone detection is the same.
The extinguishing area uses Z1 and Z2 (automatic). Fire detection uses Z3
(mixed).
Available presets are shown in the table below. The default setting is 01 (Basic
standard mode, passive end-of-line).
Table 14: Operating mode configuration presets
Display
Mode
Zone configuration Manual fire
sounder start
Actuator delay
for MCP Start
01 (default)
Basic standard
Passive end-of-line
No
Yes
02
Basic standard
Passive end-of-line,
CleanMe enabled
No
Yes
05
Basic evacuation
Passive end-of-line
Yes (operator
user level) [1]
No (bypassed)
06
Basic evacuation
Passive end-of-line,
CleanMe enabled
Yes (operator
user level) [1]
No (bypassed)
11
BS 7273 stage 1
Active EOL
No
Yes
12
BS 7273 stage 2
Active EOL
No
Yes
61
Repeater with fire
routing (EN 54-2)
N/A
N/A
N/A
63
Repeater with fire
routing (BS 7273)
N/A
N/A
N/A
00
Custom [2]
N/A
N/A
N/A
[1] A fire alarm is not required to activate the fire sounders.
[2] This option cannot be selected. It is displayed automatically when an advanced configuration
is entered