Chapter 3: Configuration and commissioning
ZP1-X3E Series Installation Manual
39
Display
Menu
Values
Extinguishing agent flow
ON/OFF
Default: Off
Fire sounders delay
00 to 10 minutes
Default: 00
Sounders operation during a zone test
ON/OFF
Default: On
Sounders re-sound
ON/OFF
Default: On
Silence sounders disabled time
00 to 10 minutes
Default: 1 minute
Fire routing delay
00 to 10 minutes
Default: 00
Battery fault check
ON/OFF
Default: On
Earth fault check
ON/OFF
Default: On
Fault latch
ON/OFF
Default: On
Module number
00 to 04
See “Expansion board function” on
page 61.
Firenet identifier
0 to 32
0: Stand-alone (no networking)
Default: 0
Firenet group. Allows you to configure
the panel to work in a 32-node network
or in a group of 32 nodes inside a 250-
node network (0000-0250)
0000 to 0218
Default: 0000
The number has four digits. Identified
by position, these are: 1234.
Press Up to enter the first two digits of
the number (positions 1 and 2).
Press Down to enter the last two digits
of the number (positions 3 and 4).
Firenet analogue remote node
0000 to 0250
Default: 0000
The number has four digits. Identified
by position, these are: 1234.
Press Up to enter the first two digits of
the number (positions 1 and 2).
Press Down to enter the last two digits
of the number (positions 3 and 4).
Firenet number of nodes [1]
2 to 32
Default: 2