Chapter 3: Configuration and commissioning
50
ZP1-X3E Series Installation Manual
Actuator delay for start manual call point
Use this menu to configure the control panel behaviour after a manual
extinguishing event (from the MCP Start point): activate the actuator immediately
or apply the actuator delay configured for automatic extinguishing events.
The default settings are:
• Basic standard mode = On
• Basic evacuation mode = Off
To configure the actuator delay for start manual call point:
1. Set the display as shown below, and then press Enter.
The red Start MCP LED flashes fast to indicate that the configuration menu is
active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
Actuator delay applies to the MCP Start.
MCP Start activates the actuator immediately (no delay).
Extinguishing agent flow
Use this menu to configure how the control panel enters into the extinguishing
released state: using extinguishing agent flow confirmation or immediately after
the activation of the actuator.
The default setting does not use extinguishing agent flow confirmation:
extinguishing agent flow OFF. Note that with this configuration the control panel
continues to provide indications of the extinguishing agent flow for information
purposes (wiring faults and activation).
If your installation requires an extinguishing agent flow signal, see “Connecting
an extinguishing agent flow device” on page 12 for more information.