Chapter 3: Configuration and commissioning
ZP1-X3E Series Installation Manual
51
To configure extinguishing agent flow:
1. Set the display as shown below, and then press Enter.
The red extinguishing agent flow LED flashes fast to indicate that the
configuration menu is active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
Extinguishing released after extinguishing agent flow
input activation.
Extinguishing released after actuator activation.
(Extinguishing agent flow indications available for
information purposes)
Fire sounder operation during a zone test
Use this menu to configure the sounder operation during a zone test. The default
setting for all operating modes is On.
To configure the sounder operation during a zone test:
1. Set the display as shown below, and then press Enter.
The Fire Sounders Start/Stop LED flashes fast to indicate that the sounder
operation during a zone test configuration menu is active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
The internal buzzer and sounders sound for 5 seconds
when an alarm is activated in a zone test.
The internal buzzer and sounders do not sound when an
alarm is activated in a zone test.