Chapter 3: Configuration and commissioning
66
ZP1-X3E Series Installation Manual
Display
Description
Value
Firenet initial zone number
0001 to 9999
Default: 0001
The number has four digits. Identified
by position, these are: 1234.
Press Up to enter the first two digits of
the number (positions 1 and 2).
Press Down to enter the last two digits
of the number (positions 3 and 4).
Firenet global controls
ON/OFF
Default: On
Firenet loop class
A/B
Default: B
Process remote zones
ON/OFF
Default: On
Firenet map
01 to 32
ON/OFF
On for nodes 1 and 2, off for the rest
Firenet repeater map
01 to 32
ON/OFF
On for nodes 1 and 2, off for the rest
Firenet analogue repeater remote node
ON/OFF
Default: Off
Firenet remote output control
ON/OFF
Default: Off
Firenet extinguishing global controls
ON/OFF
Default: Off
[1] The basic configuration setting can be replaced by a customized set of specific panels for
communication, called a Firenet map, and a set of panels to be repeated, called a Firenet
repeater map. If the configuration is changed by modifying either map, the value displayed for
Firenet number of nodes is Cu (indicating a custom network configuration).
Firenet global controls
Use this menu to configure commands (for example, reset, silence/re-sound
sounders, panel silence, cancelling delays) as local or global.
By default, this is On (controls are local but also sent to the network).
Note:
Local or global controls does not apply to disable/enable and test
commands. These are always local and sent to the control panels being
repeated. This feature provides more flexibility to configure disable/enable and
test of zones, sounders, fire routing, and fire protection.