Appendix A: Configuration presets
88
ZP1-X3E Series Installation Manual
Input and output configuration
Table 34: Inputs and outputs
IN1
Start MCP
Supervised
IN2
Hold MCP
Supervised
IN3
Abort MCP
Disable extinguishing switch (BS 7273
mode)
Supervised
Supervised
IN4
Manual-only mode activation
Unsupervised
IN5
Low pressure indication
Supervised
IN6
Extinguishing agent flow
Supervised
IN7
Safety door fault monitor
Supervised
IN8
Remote reset
Unsupervised
OUT1
Hold MCP
Unsupervised
OUT2
Abort MCP
Disable extinguishing switch (BS 7273
mode)
Unsupervised
Unsupervised
OUT3
Manual-only mode
Unsupervised
OUT4
Extinguishing released
Unsupervised
OUT5
Fire sounders
Supervised
OUT6
Extinguishing sounders
Supervised
OUT7
Extinguishing released optical warning
panels or signs
Supervised
OUT8
Actuator
Supervised
Default delays
Table 35: Default delay configuration
Fire sounders delay
0
Fire routing delay [1]
0
Zone delay
0n
Released delay
10 seconds
Flooding time
Off
Reset disabled delay
2 minutes
[1] Requires installation of optional 2010-1-SB expansion board (not supplied).