Appendix A: Configuration presets
ZP1-X3E Series Installation Manual
89
Basic configuration modes
EN 54-2 supervision and Class B fire outputs
Note:
The following presets are available for installations that do not use
EN 54-13 supervision (the SU setting is Of). See “Supervision mode” on page 33
for more information.
Basic standard mode
Fire sounders cannot be manually activated in this operating mode (fire sounders
are only activated if there is a fire alarm).
The configured actuator delay is applied when the MCP Start is activated.
Table 36: Presets and zone characteristics
Preset
Zone description
Zone detection
01
Passive EOL
Z1 and Z2 automatic, for extinguishing event
Z3 mixed, for fire detection
02
Passive EOL, CleanMe
enabled
Z1 and Z2 automatic, for extinguishing event
Z3 mixed, for fire detection
Basic evacuation mode
Fire sounders can be manually activated at the operator user level in this
operating mode (a fire alarm is not required).
The actuator is activated immediately when the MCP Start is activated.
Table 37: Presets and zone characteristics
Preset
Zone description
Zone detection
05
Passive EOL
Z1 and Z2 automatic, for extinguishing event
Z3 mixed, for fire detection
06
Passive EOL, CleanMe
enabled
Z1 and Z2 automatic, for extinguishing event
Z3 mixed, for fire detection
BS 7273 mode stage 1
Fire sounders cannot be manually activated. Fire sounders are off during the
sounders delay.
Table 38: Presets and zone characteristics
Preset
Zone description
Zone detection
11
Active EOL
Z1 and Z2 automatic, for extinguishing event
Z3 mixed, for fire detection
12
Active EOL, CleanMe
enabled
Z1 and Z2 automatic, for extinguishing event
Z3 mixed, for fire detection