Appendix A: Configuration presets
ZP1-X3E Series Installation Manual
91
Basic evacuation mode
Fire sounders can be manually activated at the operator user level in this
operating mode (a fire alarm is not required).
The actuator is activated immediately when the MCP Start is activated.
Table 43: Presets and zone characteristics
Preset
Zone description
Zone detection
05
EN 54-13 EOL
Z1 and Z2 automatic, for extinguishing event
Z3 mixed, for fire detection
Expansion board functions
EN 54-2 supervision and Class B outputs
Note:
The following expansion board presets are available for installations that
do not use EN 54-13 supervision (the SU setting is Of). See “Supervision mode”
on page 33 for more information.
Table 44: Expansion board functions (EN 54-2, Class B outputs)
Preset
ON status
Output
Delay
01
Z1 alarm
1
Yes
Z2 alarm
2
Yes
Z3 alarm
3
Yes
05
Z1 alarm
1
Yes
2
Yes
Z2 alarm
3
Yes
4
Yes
06
Z3 alarm
1
Yes
2
Yes
22
Z1 and Z2 alarm
1
Yes
2
Yes
Z2 and Z3 alarm
3
Yes
4
Yes
23
Z1 or Z2 alarm
1
Yes
2
Yes
Z2 or Z3 alarm
3
Yes
4
Yes