18
Summer / Winter Entry Set and related
differentials: Values used for adjusting
the 3-point / 0 -10 v valve. The regulation
follows the Inlet probe limiting, through
the valve control, the values of the air
temperature entered to those entered in
the two sets. If for example the winter set
is 30 C ° the valve, once the air tempera-
ture reaches this value, it closes so as not
to exceed this threshold.
Air Quality / Humidity Ventilation Set:
With Ventilation mode selection
parameter different from 0, values used
for fan control. The regulation follows the
Air Quality or humidity probe according
to the parameter value.
Ventilation Choice Mode: Indicates the
fan adjustment mode:
-Manual: The fans operate according to
the set speed, 1,2 or 3.
-Air quality: The fans automatically
change between V1 and V3 according
to the air quality set and to the relative
value read by the probe.
- Humidity: The fans change automati-
cally between V1 and V3 according to
the ventilation humidity set and to the
relative value read by the probe.
The machine, if there is a dehumidifica-
tion request, activates the integration at
regular intervals defined by this parame-
ter, in order to dehumidify the environ-
ment thanks to the cold coil, without
going to lower the room temperature
too much.
Compressor Enable Set: Value indicating
an outside air temperature limit below
which the compressor is not activated.
Travel Time 3 Point Valve: Select the
travel time of the connected valve. The
value is expressed in seconds
Choice Mode Adjustment: Defines the
mode of choice to adjust the machine
according to the methods indicated in
the image.
Hood Speed Set: Indicates the working
percentage of the fan with digital input.
The value is in percentage and can vary
between 0 and 100% Bath Speed Set:In-
dicates the working percentage of the
fan with digital input Closed Bathro-
om.The value is in percentage and can
vary between 0 and 100% Minutes.
Activation hood input:Indicates the
operating time of the hood digital input.
Once the digital input is closed, the fan
will operate according to the hood set
for this time, then it will return to normal
operation. Minutes Activate bath input:
Indicates the operating time of the
digital bath input. Once the digital input
is closed, the fan will operate according
to the hood set for this time, then it will
return to normal operation.